Teach Commands

By using teach commands, the setpoints of the switching signal channel SSC1 can be defined by teach-in
the position of the object or reference.
Next to teach-by-value which can be applied as described in section 4.3.1, using teach commands makes it
easy to compensate individual variations such as mechanical and mounting tolerances.
There are two different procedures available – static or dynamic – which can be individually chosen
independent of the switching mode of the selected SSC
Static:
-
Dynamic:
-
a time frame to define the setpoints.
The teach-in procedures are described more detailed in section 5.2 (Static) and 5.3 (Dynamic).
The switching behavior of each switching signal channel depends on the configuration (Switching Mode,
Channel Logic, ...) described in section 4.3.2.
5.1 Teach Channel Selection, TPO & Teach Status
The described teach commands can be applied to individual switching signal channels. Before proceeding
with the teach-in procedure, make sure to select the SSC that should be addressed.
Furthermore different information are available to indicate the current mode and teach-in state of the
selected switching signal channel to help to execute the right commands described in section 5.2 and 5.3.
Parameter name
TI.Select
Teach Point
Offset.TPO [%]
Teach Status.Teach
Flag SP1 TP1
Teach Status.Teach
Flag SP1 TP2
Teach Status.Teach
Flag SP2 TP1
Teach Status.Teach
State
en_BA_O200_IO-Link_V1.docx
15.08.2018/
Defines the setpoints by teach-in the positions of non-moving objects
For moving and small objects. Analyzes the minimum and maximum distances within
Short Description
Selects the SSC to which the teach-in
will be applied
Defines the offset used for the
calculation of the setpoints.
Affects the teach-in by IO-Link or
qTeach/bywire.
See the following chapters regarding the
behaviour depending on the teach-
modes
If Teach SP1 or Teach SP1 TP1 was
performed, this flag is set to Taught
If Teach SP1 or Teach SP1 TP2 was
performed, this flag is set to Taught
Only available for O200.G
Default: Idle
Rights
rw
ro
ro
ro
ro
26/34
Unit / Allowed
values
SSC1
%
Not Taught / Taught
Not Taught / Taught
Not Taught / Taught
0 = Idle
1 = SP1 Success
2 = SP2 Success
3 = SP1&2 Success
4 = Waiting for
Command
6 = Busy
7 = Error