1
2
A
Three/Four Stages. Voltage Free 2nd, 3rd & 4th Stage Activation Configuration
Common Positive
Customer Set H1 & H2 to Negative Switching (See Below)
Stage 1: Apply Power to Common +ve & Stage 1 -ve
B
Stage 2: Apply Power to Common +ve & Stage 1 -ve & connect Stage 2 -ve to Stage 1 -ve
Stage 3: Apply Power to Common +ve & Stage 1 -ve & connect Stage 3 -ve to Stage 1 -ve
Stage 4: Apply Power to Common +ve & Stage 1 -ve
& connect Stage 2 -ve & Stage 3 -ve to Stage 1 -ve
*Stage 2 only available for AB112S, AB112L or AB121L beacons
**Stage 3 only available for AB121L beacon
C
Stage 3** +ve
Stage 2* +ve
D
E
Set H1 & H2 to -ve switching
H1
F
H2
DRAWING TO BS8888:2000
DRAWN
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
J.SPILLER
ANGULAR DIMENSIONAL TOLS
CHECKED
G
B.ISARD
STANDARDS
APPROVED
SPECTRALARM RANGE
R.N.POTTS
3
4
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
RECOMMENDED MINIMUM VALUES:
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
Independent Sounder & Beacon Activation (Remove Link Wire)
-ve IN
+ve IN
Common +ve IN
Common +ve OUT
Stage 1 -ve OUT
Stage 1 -ve IN
Stage 2 -ve
Stage 3 -ve
SURFACE FINISH
WEIGHT (Kg)
DATE
28/06/2021
MATERIAL
DATE
28/06/2021
ALTERNATIVE MATERIAL
DATE
28/06/2021
5
6
SWITCHES FOR STAGE OPERATION
CUSTOMER SUPPLIED
Config.: 6
Two Stage Configuration
Independent Stage Input
Reverse Polarity Stage Monitoring
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Stage 2: Apply Power to Stage 1 +ve & Stage 1 -ve & connect Stage 2 -ve to Stage 1 -ve
*Stage 2 only available for AB112S, AB112L or AB121L beacons
+
+
-
-
Set H1 & H2 to -ve switching
H1
S2
H2
S3
Cut Link W1
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
7
8
ISSUE
MOD No.
REASON - INITIAL - DATE
INTRODUCTION
A
JS- 28/06/2021
Stage 2* +ve
-ve IN
+ve IN
Stage 1 +ve
Stage 1 -ve
Stage 2 -ve
Stage 2 +ve
ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
AB112/AB121 COMBINED SOUNDER
TITLE
& BEACON WIRING DIAGRAMS
SCALE
SHEET
DRAWING NUMBER
NTS
5
8
OF
9
10
A
Config.: 7
B
C
D
E
+
+
-
-
F
S2
A3
G
D118-06-501