Comax AB112R.230.7 Manual de instalación - Página 11
Navegue en línea o descargue pdf Manual de instalación para Equipamiento marino Comax AB112R.230.7. Comax AB112R.230.7 13 páginas.
1
2
A
Two Stage Configuration
Independent Stage Input
Line Stage Monitoring (Use suitable monitoring relays/modules)
Not to be used for reverse polarity monitoring
B
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Stage 1: Apply Power to Stage 2 +ve & Stage 2 -ve
*Stage 2 only available for AB112S, AB112L or AB121L beacons
C
Stage 2* +ve
D
E
F
Cut Link W1
DRAWING TO BS8888:2000
DRAWN
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
J.SPILLER
ANGULAR DIMENSIONAL TOLS
CHECKED
G
B.ISARD
STANDARDS
APPROVED
SPECTRALARM RANGE
R.N.POTTS
3
4
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
RECOMMENDED MINIMUM VALUES:
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
Independent Sounder & Beacon Activation (Remove Link Wires)
-ve IN
+ve IN
Stage 1 +ve
+
+
-
Stage 1 -ve
-
Stage 2 +ve
S2
Stage 2 -ve
SURFACE FINISH
WEIGHT (Kg)
DATE
28/06/2021
MATERIAL
DATE
28/06/2021
ALTERNATIVE MATERIAL
DATE
28/06/2021
5
6
SWITCHES FOR STAGE OPERATION
CUSTOMER SUPPLIED
Config.: 8
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
7
8
9
ISSUE
MOD No.
REASON - INITIAL - DATE
INTRODUCTION
A
JS- 28/06/2021
ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
AB112/AB121 COMBINED SOUNDER
TITLE
& BEACON WIRING DIAGRAMS
SCALE
SHEET
DRAWING NUMBER
NTS
6
8
OF
10
A
B
C
D
E
F
A3
G
D118-06-501