General Specifications

Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
59mW
Enclosure Type
Open Equipment
UL 61010-1 and UL 61010-2-201 File E139594, Canada & USA
Agency Approvals
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)*
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
ZIPLink Wiring System ONLY. See "Wiring Options" on page 5.
Field Wiring
Must use copper conductors 75ºC or equivalent.
See the "EU Directive" topic in the Productivity2000 Help File.
EU Directive
Information can also be obtained at:
www.productivity2000.com
Connector Type
24-Pin Molex Style 43025-2400
Weight
90g (3.2 oz)
2
www.productivity2000.com

Input Specifications

Input Channels
16
Module Signal Input Range
0–10 VDC
Signal Resolution
16-bit
Resolution Value of LSB
0–10 VDC = 152μV per count
(least significant bit)
(1 LSB = 1 count)
Data Range
0 to 65535 counts
Input Type
Single-ended (1 common)
Maximum Continuous Overload
±100V
Input Impedance
250kΩ (typical)
Filter Characteristics
Low Pass, -3dB @ 100Hz
4ms per channel
Sample Duration Time
(does not include ladder scan time)
All Channel Update Rate
112ms
Open Circuit Detection Time
Zero reading within 1s
Conversion Method
Successive approximation
Accuracy vs. Temperature
±25PPM / ºC maximum
0.1% of range
Maximum Inaccuracy
(including temperature drift)
±10 LSB maximum (±0.015% of range)
Linearity Error (end to end)
Monotonic with no missing codes
Input Stability and Repeatability
±10 LSB
Full Scale Calibration Error
±10 LSB maximum (±0.015% of range)
(not including offset)
Offset Calibration Error
±10 LSB maximum
Max Crosstalk
-76dB, ±10 LSB
External DC Power Required
24VDC (-20% / +25%) 35mA
Tech Support 770-844-4200