Autonics TZ Series Manual del producto - Página 2
Navegue en línea o descargue pdf Manual del producto para Controlador Autonics TZ Series. Autonics TZ Series 6 páginas. Dual pid control temperature controller
También para Autonics TZ Series: Manual (16 páginas), Manual (16 páginas), Manual (17 páginas), Manual (17 páginas)
![Autonics TZ Series Manual del producto](/uploads/products/server2/1931792/1931792.jpg)
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature
controller.
• When changing the input sensor, turn off the power first before changing. After changing
the input sensor, modify the value of the corresponding parameter.
• Do not overlapping communication line and power line. Use twisted pair wire for
communication line and connect ferrite bead at each end of line to reduce the effect of
external noise.
• Make a required space around the unit for radiation of heat. For accurate temperature
measurement, warm up the unit over 20 min after turning on the power.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
TZ / TZN 4 ❶ - ❷ 4 ❸
❶ Size
S: DIN W 48 × H 48 mm (TZN Series)
SP: DIN W 48 × H 48 mm (11 pin type, TZ Series)
ST: DIN W 48 × H 48 mm (TZ Series)
M: DIN W 72 × H 72 mm
H: DIN W 48 × H 96 mm
W: DIN W 96 × H 48 mm
L: DIN W 96 × H 96 mm
❷ Option output
PN Option output 1 Option output 2
1
Event
-
2
Event
Event
R
Event
PV Transmission
T
Event
Communication
A
Event
Event + PV Transmission
B
Event
Event + Communication
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety
considerations in the manuals.
Download the manuals from the Autonics website.
Software
Download the installation file and the manuals from the Autonics website.
■ DAQMaster
DAQMaster is comprehensive device management program. It is available for
parameter setting, monitoring.
Product Components
• Product, bracket × 2
[TZ4SP, TZ4ST, TZN4S] Product (+ bracket)
Sold Separately
• 11 pin socket: PG-11, PS-11 (N)
❸ OUT1 Control output
R: Relay output
S: SSR drive output
C: Current Output
• Instruction manual
• Unit sticker
• Communication converter: SCM Series
Specifications
Series
TZ/TZN Series
Power supply
100 - 240 VACᜠ 50/60 Hz ±10%
Power consumption
≤ 6 VA, TZ4SP, TZ4ST, TZN4S: ≤ 5 VA
Sampling period
500 ms
Input specification
Refer to 'Input Type and Using Range'.
Display accuracy
F.S. ±0.3% or 3℃ higher one
Relay
250 VACᜠ 3 A, 30 VDCᜡ 3 A 1c
Control
SSR
12 VDCᜡ±3 V, ≤ 30 mA
output
Current
DC 4-20 mA, load resistance: ≤ 600 Ω
Event 1/2
250 VACᜠ 1A 1a
Option
PV
DC 4 - 20 mA, load resistance: ≤ 600 Ω
output
Transmission
Comm.
RS485
Display type
7 Segment (red, green), LED type
Control type
ON/OFF, P, PI, PD, PIDF, PIDS control
Alarm output
1 to 100 (0.1 to 100.0) ℃
Hysteresis
Proportional band (P)
0.0 to 100.0%
Integral time (I)
0 to 3,600 sec
Derivative time (D)
0 to 3,600 sec
Control cycle (T)
1 to 120 sec
LBA setting
1 to 999 sec
RAMP setting
Ramp Up, Ramp Down: 1 to 99 min
• Control output: ≥ 10,000,000 operations
Mechanical
• Option output: ≥ 20,000,000 operations
Relay
• Control output: ≥ 100,000 operations
life
(load resistance: 250 VACᜠ 3 A)
cycle
Electrical
• Option output: ≥ 500,000 operations
(load resistance: 250 VACᜠ 1 A)
Between input terminal and power terminal: 2,000 VACᜠ 50/60 Hz
Dielectric strength
for 1 min
0.75 mm amplitude at frequency of 10 to 55Hz (for 1min) in each X, Y,
Vibration
Z direction for 2 hours
0.5 mm amplitude at frequency of 10 to 55Hz (for 1min) in each X, Y,
Malfunction vibration
Z direction for 2 hours
Insulation resistance
≥ 100 MΩ (500 VDCᜡ megger)
±2 kV square shaped noise by noise simulator (pulse width 1 ㎲)
Noise immunity
R-phase, S-phase
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Approval
ᜢ ᜧ ᜫ
• TZ4SP: ≈ 144 g (≈ 205 g)
• TZ4ST: ≈ 162 g (≈ 218 g)
• TZ4M: ≈ 228 g (≈ 360 g)
Unit weight
(packaged)
• TZ4W: ≈ 246 g (≈ 365 g)
• TZ4H: ≈ 246 g (≈ 365 g)
• TZ4L: ≈ 304 g (≈ 474 g)
Communication Interface
■ RS485
Comm. protocol
BCC
Application standard
EIA RS485 compliance with
Maximum connection
31 units (address: 01 to 99)
Synchronous method
Asynchronous
Comm. method
Two-wire half duplex
Comm. effective range ≤ 1,200 m
2,400 / 4,800 / 9,600 bps (parameter)
Comm. speed
Start bit
1 bit (fixed)
Data bit
8 bit (fixed)
Parity bit
None
Stop bit
1 bit (fixed)
EEPROM life cycle
≈ 1,000,000 operations (Erase / Write)
• TZN4S: ≈ 164 g (≈ 226 g)
• TZN4M: ≈ 246 g (≈ 355 g)
• TZN4W: ≈ 232 g (≈ 351 g)
• TZN4H: ≈ 232 g (≈ 351 g)
• TZN4L: ≈ 303 g (≈ 474 g)