• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T
C
3
Y
F
❶ Control output for refrigeration
1: Compressor
2: Compressor + Defrost
3: Compressor + Defrost + Evaporation-fan
Product Components
• Product
• Bracket ×2
Specifications
Series
TC3YF Series
AC
100 - 240 VACᜠ 50/60 Hz
Power supply
DC
12-24 VDCᜡ
Allowable voltage range
90 to 110% of rated voltage
AC
≤ 4 VA
Power consumption
DC
≤ 8 W
Sampling period
500 ms
Input specification
Refer to 'Input Type and Using Range'.
At room temperature (23 ±5 ℃): (PV ±0.5% or 1 ℃ higher one) rdg ±1 digit
Display accuracy
Out of room temperature range: (PV ±0.5% or 1 ℃ higher one) rdg ±1 ℃
Compressor
250 VACᜠ 5 A 1a, 30 VDCᜡ 5 A 1a
(COMP)
Control
Defrost (DEF)
250 VACᜠ 10 A 1a
output
Evaporation-fan
250 VACᜠ 5 A 1a, 30 VDCᜡ 5 A 1a
(FAN)
Display type
7 segment (red), LED type
Control type
ON/OFF Control
Hysteresis
0.5 to 5.0 ℃, 2 to 50 ℉
Mechanical
≥ 20,000,000 operations
Relay
• COMP, DEF: ≥ 50,000 operations (load resistance: 250 VACᜠ 5 A)
life cycle
Electrical
• FAN ≥ 100,000 operations (load resistance: 250 VACᜠ 10 A)
Dielectric strength
Between all external terminals and case: 2,000 VACᜠ 60 Hz for 1 min
0.75 mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X,
Vibration
Y, Z direction for 2 hours
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y,
Malfunction vibration
Z direction for 10 min
Insulation resistance
≥ 100 MΩ (500 VDCᜡ megger)
±2 kV square shaped noise (pulse width 1 ㎲) by noise simulator
AC
R-phase, S-phase
Noise immunity
±500 V square shaped noise (pulse width 1 μs) by noise simulator
DC
R-phase, S-phase
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Protection structure
IP65 (Front panel, IEC standards)
AC
ᜧ ᜣ (Except RTD option models) ᜫ
Approval
DC
Unit weight (packaged)
≈ 143 g (≈ 229 g)
Input Type and Using Range
Input type
Using range (℃)
Thermistor 5 kΩ
-40.0 to 99.9
RTD
DPt100 Ω -99.9 to 99.9
01)
01) RTD input type is option.
• Allowable line resistance per wire: ≤ 5 Ω
Errors
Display Description
ERR and error display are cross flashed when input sensor
is disconnected or sensor is not connected.
OPN
ERR and error display when if the input value is above the
input range.
HHH
ERR and error display are cross flashed if the input value is
below the input range.
LLL
ERR and error display are cross flashed when input sensor
is normal but freezer temperature does not change more
LBA
than 1.0 ℃ (2 ℉) during loop break alarm (LBA) time.
• When an error occurs, the compressor is operated to protect the control object according to the 'Error,
compressor operation cycle/duty ratio' parameter setting values.
-
R
❷ Power supply
1: 12-24 VDCᜡ
4: 100-240 VACᜠ 50/60 Hz
• Instruction manual
• NTC sensor (5 kΩ) × 1
Using range (℉)
-40 to 212
-148 to 212
Troubleshooting
Check input sensor
status.
When input is within the
rated input range, this
display disappears.
Check setting method.
Connections
FAN OUT:
250 VACᜠ 5 A
30 VDCᜡ 5 A
RESISTIVE LOAD
-
-
-
-
-
1
2
3
4
5
A
B
B'
RTD
SENSOR
NTC
Crimp Terminal Specifications
• Unit: mm, Use the crimp terminal of follow shape.
Wire ferrule
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
72
■ Panel cut-out
≥ 91
68
+0.7
0
■ NTC sensor (5kΩ)
AWG22
TPE lead wire
Soldering
≤ 15
2000 ±50
Installation Method
Mount the product to panel with bracket, fasten the bolts by using screwdriver..
COMP OUT:
DEF OUT:
250 VACᜠ 5 A
250 VACᜠ 10 A
30 VDCᜡ 5 A, 1a
RESISTIVE LOAD
RESISTIVE LOAD
-
-
-
-
-
-
6
7
8
9
10
11
SOURCE
100-240 VACᜠ
4 VA 50/60 Hz
12-24 VDCᜡ 8 W
6
≤ 4.0
≤ 1.9
6
77
■ Bracket
60
5±1