Autonics TC3YF Series Manual del producto - Página 3

Navegue en línea o descargue pdf Manual del producto para Controlador de temperatura Autonics TC3YF Series. Autonics TC3YF Series 4 páginas. Refrigeration temperature controllers

Autonics TC3YF Series Manual del producto
Unit Descriptions
1
2
1. Temperature display part (Red)
Run mode: Displays PV (Present value)
Setting mode: Displays parameter name
2. Indicator
Display Name
Description
Displays deviation of PV (Present value) based on SV (Setting
Deviation
value).
Compressor
Turns ON when compressor output is ON.
COMP
output
Flashes when output is OFF or protection operation.
Turns ON when defrost output is ON.
DEF
Defrost output
Flashes when defrost delay operation.
Evaporation-fan
Turns ON when evaporator-fan output is ON.
FAN
output
Flashes when evaporator-fan output delay operation.
℃, ℉
Temperature unit
Displays selected unit (parameter).
Mode Setting
SV setting
[MD]
→ Parameter 1 group
[MD] 3 sec
→ Parameter 2 group
[MD] 5 sec
RUN
Manual defrost
[▲] over 3 sec
execution
Auto when
Loop break alarm
conditions are
satisfied
Parameter Setting
• Some parameters are activated/deactivated depending on the model or setting of
other parameters. Refer to the descriptions of each item.
• [MD] key: Move to next item after saving / Return to RUN mode after saving (≥ 3 sec)
[▲], [▼] key: Select parameter / Change setting value
■ Parameter 1 group
Parameter
Display Default Setting range
1-1
Hysteresis
!0 0.5 to 5.0 ℃, 2 to 50 ℉
HYS
1-2
Defrost cycle
DIN
1-3
Defrost Time
30 0 to 59 min
DET
1-4
LBA time
LBA
1-5
Input correction
)0 -10.0 to 10.0 ℃, -18 to 18 ℉
INB
1-6
SV low limit
-4)0 Refer to 'Input Type and Using
LSV
1-7
SV high limit
HSV
9(9
■ Parameter 2 group
Parameter
Display Default Setting range
Compressor start
2-1
up delay and
)20 0 min 10 sec to 9 min 59 sec
SDL
restart delay time
Compressor Min.
2-2
)20 0 min 10 sec to 5 min 00 sec
operation time
ONT
Defrost end delay
2-3
and evaporator-
!00 0 min 00 sec to 5 min 59 sec
DRP
fan delay time
Evaporation-fan
2-4
operation mode
FAN
EF1
Error, compressor
2-5
operation cycle
CLE
Error, compressor
2-6
50 0 to 100%
duty ratio
DUT
2-7
Temperature unit
?C ℃, ℉
UNT
2-8
Lock
LOC
OFF
3
2
3. Input key
Display
Name
[MD]
Mode key
[▲], [▼]
Setting value control key
Change value: [▼], [▲]
Save: [MD] or no key
input over 60 sec
[MD] over 3 sec
[▼] over 3 sec
Release: [▼] + [▲] over 3
(LBA)
sec
4 0 (manual defrost) to 24 hours
0 0 to 999 sec
Range.
Refer to 'Evaporation-fan Operation
Mode'
0 0 to 20 min
OFF: No lock
LC.1: Parameter 2 group lock
LC.2: Parameter 1, 2 group lock
LC.3: Parameter 1, 2 Group, SV
setting mode lock
Evaporation-fan Operation Mode
• Output does not turn ON but the dedicated indicator flashes at the compressor,
defrost, evaporator-fan delay period (■).
Start-up
Compressor
delay
operation
Comp
-ressor
Defrost
cycle
Defrost
EF1
Evaporator-fan delay
EF2
EF3
EF4
EF5
Power ON
Parameter Description
When compressor operates, evaporator-fan also operates. When compressor
operation is finished, evaporator-fan also operation turns OFF.
EF1
When compressor operates, evaporator-fan operates after the set evaporator-
fan start-up delay time. When compressor operation is finished, evaporator-fan
EF2
operation turns OFF. (regardless of defroster operation)
When power turns ON, evaporator-fan operates. When defroster operates,
evaporator-fan stops. (regardless of compressor operation)
EF3
Evaporator-fan operates only when operating compressor or defrost. Evaporator-
fan stops when compressor and defroster stops. (for above zero temperature
EF4
control)
Evaporator-fan operates from power ON to power OFF. (regardless of compressor,
defroster operation)
EF5
RUN
Condition
-
-
-
-
-
-
Condition
-
-
-
-
-
2-5 Error,
compressor
operation
cycle: > 0
-
-
Defroster operation period
Defroster operation period
Compressor
Defroster
Defroster
operation
operation
operation
Defrost
Defrost
end
end
Defrost
Defrost
Defrost
delay
delay
time
cycle
time
Evaporator-fan delay
Compressor
operation
Defrost
Defrost
cycle
time
Evaporator-fan delay