Autonics TMH Series Manual de inicio rápido - Página 3

Navegue en línea o descargue pdf Manual de inicio rápido para Controlador de temperatura Autonics TMH Series. Autonics TMH Series 6 páginas. Modular2/4-channel pid temperature controllers with screw connector

Autonics TMH Series Manual de inicio rápido
■ Communication module
Model
TMHC-22LE
• Connection type: RS422 / RS485
COM1
• Protocol: Modbus RTU,
Communi
PLC Ladderless
COM2
-cation
communication
PC loader TTL (Protocol: Modbus RTU)
Double insulation or reinforced insulation (mark: 回, dielectric strength
Insulation type
between the measuring input part and the power part: 1 kV)
Unit weight
≈ 147 g (≈ 219 g)
(packaged)
■ Common
Power supply
24 VDCᜡ
01)
Allowable voltage
90 to 110% of rated voltage
range
Power Consumption ≤ 5 W (for max. load)
Display type
None- parameter setting and monitoring is available at external devices
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Insulation resistance 100 MΩ (500 VDCᜡ megger)
1,000 VACᜠ 50/60 Hz for 1 min (between input terminals and power
Dielectric strength
terminals)
0.75mm amplitude at frequency of 5 to 55Hz (for 1 min) in each X, Y, Z
Vibration
direction for 2 hours
Noise immunity
Square shaped noise by noise simulator (pulse width 1 μs) ±0.5 kV
Ambient
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
temperature
Ambient humidity
35 to 85%RH, Storage: 35 to 85%RH (no freezing or condensation)
Accessory
Expansion connector: 1, module lock connector: 2
Protection structure IP20 (IEC standard)
Approval
ᜢ ᜧ ᜣ ᜫ
01) The control extension/option/communication module uses the power voltage from the control basic module.

Input Specifications

■ Input type and range
The setting range of some parameters is limited when using the decimal point display.
Decimal
Input type
point
1
K (CA)
0.1
1
J (IC)
0.1
1
E (CR)
0.1
1
T (CC)
0.1
B (PR)
1
Thermo
R (PR)
1
-couple
S (PR)
1
N (NN)
1
C (TT)
1
G (TT)
1
1
L (IC)
0.1
1
U (CC)
0.1
Platinel II
1
Cu50 Ω
0.1
Cu100 Ω
0.1
JPt100 Ω
1
JPt100 Ω
0.1
RTD
DPt50 Ω
0.1
DPt100 Ω
1
DPt100 Ω
0.1
Nickel120 Ω 1
0 to 10 V
-
0 to 5 V
-
1 to 5 V
-
Analog
0 to 100 mV
-
0 to 20 mA
-
4 to 20 mA
-
• Permissible line resistance per line: ≤ 5 Ω
■ Measurement accuracy
Input type Using temperature
Measurement accuracy
(PV ±0.3% or ±1 ℃ higher one) ±1-digit
• Thermocouple K, J, T, N, E below -100 ℃ and L, U, PLII,
At room temperature
(23 ±5 ℃)
• Thermocouple C, G and R, S below 200 ℃:
Thermo
• Thermocouple B below 400℃: there is no accuracy
-couple
RTD
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
• RTD Cu50 Ω, DPt50 Ω:
Out of room
temperature range
• Thermocouple R, S, B, C, G:
• Other sensors: ≤ ±5 ℃ (≤-100 ℃)
At room temperature
±0.3% F.S. ±1-digit
(23 ±5 ℃)
Analog
Out of room
±0.5% F.S. ±1-digit
temperature range
• Connecting 1 or more expansion module can vary measurement accuracy about ±1℃, regardless of the number
of connected expansion module.
TMHC-22EE
• Connection type: Ethernet
• Protocol: Modbus TCP
≈ 129 g (≈ 200 g)
Display
Input range (℃)
Input range (℉)
Method
K (CA) .H
-200 to 1,350
-328 to 2,463
K (CA) .L
-200.0 to 1,350.0
-328.0 to 2463.0
J (IC) .H
-200 to 800
-328 to 1,472
J (IC) .L
-200.0 to 800.0
-328.0 to 1472.0
E (CR) .H
-200 to 800
-328 to 1,472
E (CR) .L
-200.0 to 800.0
-328.0 to 1,472.0
T (CC) .H
-200 to 400
-328 to 752
T (CC) .L
-200.0 to 400.0
-328.0 to 752.0
B (PR)
0 to 1,800
R (PR)
0 to 1,750
S (PR)
0 to 1,750
N (NN)
-200 to 1,300
-328 to 2,372
C (TT)
0 to 2,300
G (TT)
0 to 2,300
L (IC) .H
-200 to 900
-328 to 1,652
L (IC) .L
-200.0 to 900.0
-328.0 to 1,652.0
U (CC) .H
-200 to 400
-328 to 752
U (CC) .L
-200.0 to 400.0
-328.0 to 752.0
PLII
0 to 1,390
CU 50
-200.0 to 200.0
-200.0 to 392.0
CU 100
-200.0 to 200.0
-200.0 to 392.0
JPt100.H
-200 to 650
-328 to 1,202
JPt100.L
-200.0 to 650.0
-328.0 to 1,202.0
DPt50.L
-200.0 to 600.0
-328.0 to 1,202.0
DPt100.H
-200 to 650
-328 to 1,202
DPt100.L
-200.0 to 650.0
-328.0 to 1,202.0
NI12
-80 to 260
-112 to 500
AV1
0 to 1,000
AV2
0 to 5,000
AV3
1,000 to 5,000
AMV1
0 to 1,000
AMA1
0 to 2,000
AMA2
400 to 2,000
RTD Cu50 Ω, DPt50 Ω:
(PV ±0.3% or ±2 ℃ higher one) ±1-digit
(PV ±0.3% or ±3 ℃ higher one) ±1-digit
standards
(PV ±0.5% or ±3 ℃ higher one) ±1-digit
(PV ±0.5% or ±5 ℃ higher one) ±1-digit

Communication Setting

■ Interface
(10BaseT)
Module
Series
Protocol
Comm. method
Maximum
connection
Synchronization
type
Connection
method
Comm. effective
range
Comm. speed
Response time
Start bit
Data bit
Parity bit
Stop bit
• When changing the setting value related to communication interface, reboot the device for normal operation.
• It is recommended to use Autonics communication converter. Please use twisted pair wire, which is suitable for
RS485 communication.
■ Address
Set the communication address with the communication address setting switch (SW1,
default: 1) and communication address group switch (SW2, default: +0, TMH2/4 series).
SW1
Series
+0
+16
TMH2/4
+0
+16
TMHC
TMHA
TMHE
TMHCT
32 to 3,272
• When connecting TMHC and TMH2/4 to master separately, communication address can be duplicated, but if they
32 to 3,182
communicate with master at the same time, communication address must not be duplicated to avoid error.
(use address TMHC: 1 to 16, TMH2/4: 17 to 32)
32 to 3,182
■ Mac address [Ethernet communication module]
32 to 4,172
It is possible to check Mac address for Ethernet communication at DAQMaster.
32 to 4,172
Refer to the manual for the details.
■ DIP switch setting [Ladderless communication module]
After separating base terminal block, set communication speed, stop bit, PLC
32 to 2,534
connection and protocol by using a internal DIP switch.
• Setting values are applied to COM1 only, default: All switches OFF (following parameter
setting)
DIP SW1
1
2
OFF
OFF
OFF
ON
ON
OFF
ON
ON
DIP SW2
1
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
Control
Option
TMHA, TMHE,
TMH2/4
TMHCT
Modbus RTU
RS485
32 units (address:
01 to 32)
• 16 units in case of
16 units per
connecting TMHC
each module
module
(address: 01 to 16)
Asynchronous
Two-wire half duplex
≤ 800 m
4,800 / 9,600 (default) / 19,200 / 38,400 / 115,200 bps
(parameter)
5 to 99 ms (default: 20 ms)
1 bit (fixed)
8 bit (fixed)
None (default) , Odd, Even
1 bit, 2 bit (default)
0
1
2
3
4
5
6
7
16
01
02
03
04
05
06
07
32
17
18
19
20
21
22
23
16
01
02
03
04
05
06
07
48
33
34
35
36
37
38
39
64
49
50
51
52
53
54
55
80
65
66
67
68
69
70
71
DIP SW1
Communication speed
3
4
Following parameter setting
OFF
OFF
19,200 bps
OFF
ON
38,400 bps
ON
OFF
115,200 bps
ON
ON
3
4
PLC connection and protocol
OFF
OFF
Following parameter setting
OFF
ON
Modbus RTU
ON
OFF
LS MASTER-K series special protocol
ON
ON
LS GLOFA-GM series special protocol
OFF
OFF
LS XGT/XGB series special protocol
MITSUBISHI MELSEC series special protocol
OFF
ON
Q/QnACPU common command (1401/0401)
MITSUBISHI MELSEC series special protocol
ON
OFF
ACPU common command (WW/WR)
ON
ON
OMRON SYSMAC series special protocol
OFF
OFF
MITSUBISHI MELSEC3 series special protocol
Communication
TMHC-22LE
TMHC-22EE
Modbus RTU,
PLC Ladderless
Modbus TCP
communication
RS422, RS485
Ethernet (10BaseT)
Control module 16 units, option
module 16 units per each module
(32 units in total)
-
-
-
10 Mbps
-
-
-
-
-
8
9
A
B
C
D
E
F
08
09
10
11
12
13
14
15
24
25
26
27
28
29
30
31
08
09
10
11
12
13
14
15
40
41
42
43
44
45
46
47
56
57
58
59
60
61
62
63
72
73
74
75
76
77
78
79
DIP SW2
OFF
ON
Stop bit
Following parameter setting
Stop bit: 1 bit
Stop bit: 2 bit
-