AGS Merlin GDP4 Manual del usuario - Página 5
Navegue en línea o descargue pdf Manual del usuario para Detectores de gas AGS Merlin GDP4. AGS Merlin GDP4 12 páginas. Gas safety products, gas detection panel
Merlin GDP4
2.4 EM REMOTE (Remote emergency shut off buttons)
The terminal for remote emergency shut-off buttons is detailed on the
circuit board as [EM REMOTE].
These connections are linked out as a factory setting.
Remote emergency shut-off buttons should be volt free and wired to
the Merlin GDP4 using two-core cable.
2.5 HEAT SENSOR
The terminal for heat detectors is detailed as [HEAT SENSOR].
These connections are linked out as a factory setting.
Heat detectors should be volt free and wired to the Merlin GDP4 using two-
core cable.
2.6
FIRE PANEL
The terminal for fire alarms is detailed as [FIRE PANEL].
These connections are linked out as a factory setting.
Fire alarms should be volt free and wired to the Merlin GDP4 using two-
core cable.
2.8
SOUNDER/STROBE
The terminal for audible/visual alarms is detailed on the circuit board as
[SOUNDER/STROBE].
Sounder alarms should be wired using low voltage cable and wired to the
Merlin GDP4 using two-core cable.
This terminal has a 24VDC output.
Rev: 06 05-19
2.7
BMS OUT
Terminal connections are available on the circuit board for connections
to Building Management Systems etc.
Marked on the circuit board as [BMS OUT - N/O - COM - N/C] these are
volt free connections.
User Guide
5