Settings Menu

The Parksafe panel has a touch screen which allows the engineer/user to configure the system.
Adjust the screen brightness.
(Press or slide the cursor up and down)

Menu Options Explained

FUNCTION
Auto Start
0-10V Minimum Value
Alarm Time Delay
Damper Follows
Temperature Alarm

Factory Set Condition

Auto Start
0-10V Minimum Value
Alarm Time Delay
Damper Follows
Temperature Alarm
Rev: 13
0721
OPTION
Explanation
- ON
In the event of a power loss - the Parksafe panel will automatically restart when
power is restored, or not.
- OFF
- 0 or 2V
0-10V terminal output under normal / safe conditions.
Time (minutes) for alarm relay to switch when detectors reach alarm status.
- 5 to 25
(Following second relay Output 2). 5, 10, 15, 20 or 25minutes,
- Output 1
The Damper relay output can switch together with either [OUTPUT 1], [OUTPUT 2]
- Output 2
or the [ALARM] relays.
- Alarm
All Relays except Alarm will switch when the defined temperature (F°) is exceeded.
- >68 to 86°F
Select Off to disable function. Relays switch back when defined temperature
- Off
reaches 4°F below selected threshold.
- ON
Panel will restart following a power cut/loss.
- 0V
No voltage output under normal condition status.
Following Output 2 relay switching, the Alarm relay will activate after five (5)
- 5
minutes.
- Output 1
Damper relay switches with [Output 1] relay.
- Off
Temperature alarm disabled.
.
Change/select option