AGS Parksafe Control Panel Kurulum Operasyon ve Bakım - Sayfa 9

Kontrol Paneli AGS Parksafe Control Panel için çevrimiçi göz atın veya pdf Kurulum Operasyon ve Bakım indirin. AGS Parksafe Control Panel 16 sayfaları. Ventilation control panel
Ayrıca AGS Parksafe Control Panel için: Kurulum ve Kullanım Kılavuzu (16 sayfalar), Kurulum ve Kullanım Kılavuzu (16 sayfalar), Kurulum, Çalıştırma ve Bakım Kılavuzu (20 sayfalar)

AGS Parksafe Control Panel Kurulum Operasyon ve Bakım
Installation, Operation & Maintenance

Settings Menu

The Parksafe panel has a touch screen which allows the engineer/user to configure the system.
Adjust the screen brightness.
(Press or slide the cursor up and down)

Menu Options Explained

FUNCTION
Auto Start
0-10V Minimum Value
Alarm Time Delay
Damper Follows
Temperature Alarm

Factory Set Condition

Auto Start
0-10V Minimum Value
Alarm Time Delay
Damper Follows
Temperature Alarm
Rev: 13
0721
OPTION
Explanation
- ON
In the event of a power loss - the Parksafe panel will automatically restart when
power is restored, or not.
- OFF
- 0 or 2V
0-10V terminal output under normal / safe conditions.
Time (minutes) for alarm relay to switch when detectors reach alarm status.
- 5 to 25
(Following second relay Output 2). 5, 10, 15, 20 or 25minutes,
- Output 1
The Damper relay output can switch together with either [OUTPUT 1], [OUTPUT 2]
- Output 2
or the [ALARM] relays.
- Alarm
All Relays except Alarm will switch when the defined temperature (F°) is exceeded.
- >68 to 86°F
Select Off to disable function. Relays switch back when defined temperature
- Off
reaches 4°F below selected threshold.
- ON
Panel will restart following a power cut/loss.
- 0V
No voltage output under normal condition status.
Following Output 2 relay switching, the Alarm relay will activate after five (5)
- 5
minutes.
- Output 1
Damper relay switches with [Output 1] relay.
- Off
Temperature alarm disabled.
.
Change/select option
(Press the blue option box or press and hold)
Parksafe Control Panel
9