Maintronic Casambi CBA UP Manual - Página 17
Navegue en línea o descargue pdf Manual para Controlador Maintronic Casambi CBA UP. Maintronic Casambi CBA UP 20 páginas. Blind actuator
También para Maintronic Casambi CBA UP: Manual (12 páginas)
4.4 Calibration
Once the device is added into a Casambi network,
a calibration can be performed..
Perform calibration drive (Drive time)
To ensure proper operation, a calibration drive
must be performed during initial startup.
1. Therefore, run a complete cycle (0% fully open
to 100% fully closed) and measure the drive
time.
2. In order to take into effect deviations in the
travel time from bottom to top, the cycle
(from 100% completely closed to 0% comple-
tely open) can be measured again.
3. Enter the measured time plus approx. 1 se-
cond (as a buffer) in the device settings under
parameter „Drive Time".
Manual english
17
Setting the slat position (Angle time)
The „Angle Time" is the aperture angle of the
blind slats, this time must be measured and set in
the parameters
1. Move the blind up a little until the slats are in
a horizontal position.
2. Now move the blind downwards and stop the
time until the slats are closed.
3. Set the measured time in ms in the parame-
ters under „Angle Time".
Set drive direction
If the drive direction is not correct, the parameter
„Swap Controls Up/Down" can be used to swap
the direction.
Casambi blind actuator