5 Section of FCU

5.1 FCU Type Selection

The air-water fan coil unit is optional for Versati units

5.2 Matching of Capacity

Load of the FCU is better to be between 70%~120% of the Versati unit.
Notes:
When load of the FCU is too small, the unit would start/stop frequently, which is adverse for oil return.
When load of the FCU is too large, the unit would always run under high frequency, which is unhelpful for
energy conservation.
Air Volume
Type
3
(m
/h)
Wall mounted
166~1020
type
Concealed
213~2380
ceiling type
Floor ceiling
213~2040
type
Cassette type
480~1700
Cooling
Heating
Capacity
Capacity
(kW)
(kW)
2.1~5.4
3.15~8.5
1.85~12.8
3.1~21
1.9~10.8
2.8~16.2
4.5~9
6.8~13.7
7
Static
Pressure
(Pa)
——
12, 30
——
——
Design & Selection
Appearance