- ページ 9
ヒートポンプ Gree Versati II SeriesのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Gree Versati II Series 13 ページ。 Air-to-water heat pump monobloc versati
Gree Versati II Series にも: サービスマニュアル (18 ページ)
5 Section of FCU
5.1 FCU Type Selection
The air-water fan coil unit is optional for Versati units
5.2 Matching of Capacity
Load of the FCU is better to be between 70%~120% of the Versati unit.
Notes:
When load of the FCU is too small, the unit would start/stop frequently, which is adverse for oil return.
①
When load of the FCU is too large, the unit would always run under high frequency, which is unhelpful for
②
energy conservation.
Air Volume
Type
3
(m
/h)
Wall mounted
166~1020
type
Concealed
213~2380
ceiling type
Floor ceiling
213~2040
type
Cassette type
480~1700
Cooling
Heating
Capacity
Capacity
(kW)
(kW)
2.1~5.4
3.15~8.5
1.85~12.8
3.1~21
1.9~10.8
2.8~16.2
4.5~9
6.8~13.7
7
Static
Pressure
(Pa)
——
12, 30
——
——
Design & Selection
Appearance