6. Specifications
Power
Switch AC: 85 – 250 VAC, 50/60Hz, 1 Phase
Supply:
Switch DC: 10-30 VDC
Fuse: 10A, 250V, Time Delay, 5 x 20mm
Command Signal In
Voltage: -0.8 to 10.8 VDC
Current: 0 to 23 mA
135Ω Command: 150 Ω maximum (20mA excitation current)
Resistance:
24 VDC maximum
On-Off:
< 10V = Off
≥ 10V = On
Resolution: 12 bit
Feedback Signal Out
Voltage: 0 to 10.8 VDC
Current: 0 to 21.5 mA
Load: Up to 400Ω@12VDC to 1000Ω@24VDC
Resolution: 12 bit
Position Feedback
Voltage: 0 to 3.3 VDC
Potentiometer: 1kΩ
Limit Switches: Normally Open
Outputs
+24V Out: 24VDC, 30mA maximum
Ext. Brake: 300mW, 350V, 120mA continuous load
Environmental
Operating: 0°C to 60°C (32°F to 140°F)
Storage: -40°C to 85°C (-40°F to 185°F)
Relative Humidity: 0 to 90% non-condensing
Connections
TMC-4A002-001: 0.15" pitch, 16 – 30 AWG (0.05 – 1.3 mm
Terminals:
TMC-4A002-002: 5mm pitch, 14 - 26 AWG (0.2 - 2.5 mm
Headers: 0.1" pitch, 2pos and 3pos
TMC-4A002-001: 2x7 pos, 2mm pitch
Expansion Header:
TMC-4A002-002: 2x7 pos, 0.1" pitch
www.atcontrols.com
1kΩ Command: 1.1 kΩ maximum (2.7mA excitation current)
2
18
TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
2
)
)
IOM08139 REVISION 01
03/18/21