Installing the SS-100

The CPC SS-100 Serial Server (P/N 570-
2000) is a device that allows CPC's RE-
FLECS controllers (RMCC, BEC, or BCU)
and Einstein controllers to communicate with
a PC running UltraSite32 using the control-
ler's serial port. Traditionally, REFLECS and
Einstein controllers have relied on a modem or
a serial cable connection to interface with Ul-
traSite. With an SS-100 installed, the RE-
FLECS or Einstein can be integrated with a
company's existing LAN or WAN.
A kit is included with the SS-100, which
consists of:
• 5V power supply
• 10' DB9 serial cable
• 9-pin (DB9) to 9-pin connector
• 9-pin to 25-pin (DB25) connector (STC)
1.1.
Working with the Network
Administrator
Like other computers on the network to which it is at-
tached, the SS-100 is also a network node. Because of this,
it is important to work with the network administrator.
Without the cooperation of the network administrator, it
will be difficult to make the SS-100 function properly.
1.2.

IP Address Specification

An IP address and subnet mask are denoted as a series
of four decimal numbers separated with periods. Each
number has a value between 0 and 255.
The following are examples of valid IP addresses and
subnet masks. The actual numbers used as IP addresses
must be determined by the network administrator.
IP Address
Subnet Mask
"Empty" IP Address
1.3.

Network Considerations

Like any other node on the network, the SS-100 must be
assigned an IP address. For this reason, the network admin-
istrator's input is required for the SS-100 installation. Ob-
SS-100 Serial Server
192.168.1.33
255.255.255.0
0.0.0.0
tain the following information from the network
administrator before configuring the SS-100.
• UltraSite PC IP address (required)
• SS-100 IP address (required)
• Subnet mask (required)
• Primary DNS IP address (may not be re-
quired)
• Secondary DNS IP address (may not be re-
quired)
• Primary gateway IP address (may not be
required)
• Secondary gateway IP address (may not be
required)
1.4.
Ethernet Network Wiring and
Wire Types
To connect the SS-100 to an existing Ethernet network,
use the same standard Category 5 network cable used by
the rest of the network. If the SS-100 is being wired as part
of a brand new Ethernet network installation, consult your
network administrator or IS technician for the proper wire
type.
In either case, you will need to crimp an RJ45 connector
to the end of the network cable segment that will connect to
the SS-100.
Installing the SS-100 • 7