SYSTEM START-UP
1. Braze and check all field-made refrigerant joints for leaks and repair as necessary. See
the EarthLinked
Maintenance Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start
Manual for the proper procedure.
2. Evacuate and charge the refrigerant system in accordance with the appropriate
EarthLinked
Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start Manual.
3. Fill the water system and ensure that all air has been eliminated from the desuperheater,
to prevent pump cavitation and bearing damage.
4. Check and repair all field-made water system joints to ensure there are no leaks.
5. Start system and check for functionality.
DSH KIT (04/13)
®