EarthLinked DSH-1872 Manual - Halaman 20

Jelajahi secara online atau unduh pdf Manual untuk Pendingin Udara EarthLinked DSH-1872. EarthLinked DSH-1872 20 halaman. Desuperheater

SYSTEM START-UP

1. Braze and check all field-made refrigerant joints for leaks and repair as necessary. See
the EarthLinked
Maintenance Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start
Manual for the proper procedure.
2. Evacuate and charge the refrigerant system in accordance with the appropriate
EarthLinked
Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start Manual.
3. Fill the water system and ensure that all air has been eliminated from the desuperheater,
to prevent pump cavitation and bearing damage.
4. Check and repair all field-made water system joints to ensure there are no leaks.
5. Start system and check for functionality.
DSH KIT (04/13)
®
Heating and Cooling System Installation, Operation and
®
Heating and Cooling System Installation, Operation and Maintenance
Page 20