Dell EMC PowerSwitch S6100-ON Manual de instalación - Página 23
Navegue en línea o descargue pdf Manual de instalación para Interruptor Dell EMC PowerSwitch S6100-ON. Dell EMC PowerSwitch S6100-ON 48 páginas.
To remove the system from the rack, loosen the screws and slide the system out of the rack.
Figure 17. S6100–ON system installation
1. Extra screws to restrict front-back movement of the switch
2. Main screw
Chassis ground
After you mount the chassis, secure the chassis ground as follows:
To properly ground the chassis, Dell recommends using the two-hole lug shipped in a separate plastic bag with your chassis. The
two-hole lug must be a UL recognized, crimp-type lug. To connect the ground cable to the framework or cabinet and to mount
the unit, use thread-forming unit mounting screws that remove paint or nonconductive coatings.
CAUTION:
Grounding conductors must be made of copper. Do not use aluminum conductors.
NOTE:
The rack installation ears are not suitable for grounding.
NOTE:
Coat the two-hole lug with an anti-oxidant compound before crimping. Also, bring any unplated mating surfaces to a
shiny finish and coat with an anti-oxidant before mating. Plated mating surfaces must be clean and free from contamination.
NOTE:
Never use the same bolts to secure multiple grounding cables.
1. Locate the chassis ground lug nuts and holes on the chassis back.
S6100–ON installation
23