▶ Following installation, ensure a controlled restart.
Risk of short-circuit or escape of media through leaking
screw joints.
▶ Ensure seals are seated correctly.
▶ Carefully screw together coil and device socket or valve and
pipelines.
5.2 Fluid installation
Follow the safety instructions under "5.1".
Installation can be in any position, preferably actuator upright.
→
Before installation, clean any possible dirt off the pipelines.
→
For Type 0283 install a strainer (≤ 500 µm) upstream of the
valve inlet. Type 0293 DN20 already has the strainer integrated
in the valve.
→
With type 0293 DN25, a strainer (<=500μm), e.g. our type
TFU001, which is accessible for maintenance work, must be
installed upstream of the valve in accordance with DIN EN 161
→
Seal the pipe connection with PTFE tape.
Attention: The PTFE tape must not get into the device.
→
Observe direction of flow (see "Fig. 3").
NOTE!
Caution risk of breakage.
▶ Do not use the coil as a lever arm.
→
Hold the device with an open-end wrench on the housing and
screw into the pipeline.
Fig. 5:
Identification of flow direction
english
Identification for flow
direction
9