▶ Following installation, ensure a controlled restart.
Risk of short-circuit or escape of media through leaking
screw joints.
▶ Ensure seals are seated correctly.
▶ Carefully screw together coil and device socket or valve and
pipelines.
5.2 Fluid installation
Follow the safety instructions under "5.1".
Installation can be in any position, preferably actuator upright.
Before installation, clean any possible dirt off the pipelines.
For Type 0283 install a strainer (≤ 500 µm) upstream of the
valve inlet. Type 0293 DN20 already has the strainer integrated
in the valve.
With type 0293 DN25, a strainer (<=500μm), e.g. our type
TFU001, which is accessible for maintenance work, must be
installed upstream of the valve in accordance with DIN EN 161
Seal the pipe connection with PTFE tape.
Attention: The PTFE tape must not get into the device.
Observe direction of flow (see "Fig. 3").
NOTE!
Caution risk of breakage.
▶ Do not use the coil as a lever arm.
Hold the device with an open-end wrench on the housing and
screw into the pipeline.
Fig. 5:
Identification of flow direction
english
Identification for flow
direction
9