Header Inserts (Part #50055-1 for
1 1/2"; #50055-2 for 2") are used
in special situations where
unusually high stagnation
temperatures are expected,
such as in a desert climate
or where abnormally high
system pressures may occur.
Use four (4) inserts per collector.
9
The Optional Supplemental High Wind Area
Collector Hold-Down Kit (Part #12035-1 for 1 1/2",
#12035-2 for 2") used in addition to the basic collector
installation kit in regions where high winds are prevalent.
Requires twice the amount of hold-down strap.
DISTANCE BETWEEN PANEL
HEADERS AND STRAPS
Collector
Collector
Collector
Panel Size
(A) Distance
(B) Distance
in feet
inches (cm)
inches (cm)
_________
_________
_________
12
60 (152)
10
48 (122)
16 (40)
8
36 (91)
6
24 (60)
_____
4
MOUNTING THE SOLAR COLLECTORS
Refer to Figure 1 throughout this section. When mounting
the collectors, always make provisions for inlet connec-
tions at the bottom header and outlet connections at the
top. The outlet headers must be pitched a vertical dis-
tance of at least 8" (20cm) above the inlet headers to
assure proper drainage and uniform flow. Plan the col-
lector location to allow at least one foot on all sides of the
row of collectors for mounting brackets and piping. The
outlet pipe for each row of collectors must be connected
diagonally opposite the inlet pipe. Refer to Figure 2.