and keep enough space around the inverter.
The protective grounding must be connected to the ground. The
cross section of wire should not be less than 4mm
A fuse or breaker should be used between battery and inverter,
the value of fuse or switch should be twice of the inverter rated
input current.
The wire connects between battery and inverter should be
shorter than 3m, the current density should be less than
3.5A/mm
longer than 3m, the current density should be reduced.
Do not connect the battery charger or similar devices to the
input terminal of the inverter.
Do not put the inverter close to the flooded lead-acid battery
because the sparkle in the terminals may ignite the hydrogen
released by the battery.
It‟s an off-grid inverter, do not connect the AC output terminals
to the grid or electrical source, otherwise the inverter may be
damaged.
This inverter can only be used singly, parallel connection or in
series will damage the inverters.
Risk of electric risk, don‟t touch output port when the inverter is
working. The output is forbidden to connect other power,
otherwise the inverter will be damaged. The inverter must be in
off, when connecting load.
Do not attempt to repair the fault inverter yourself, otherwise it
may lead to a serious accident. Please contact the manufacture‟
s engineer.