5.
After aiming is complete, tighten all bolts and screws including hex and set screws on side of fixture and mounting
hardware.
6.
Briefly turn the laser back on or re-check view through tube to verify that the luminaire aim did not shift during
tightening.
7 .
Remove the aiming mount from the fixture and proceed to the next luminaire.
Final aiming:
Aiming information is exported from computer lighting simulation software. Since on site conditions may vary from the
computer models, final aiming is usually required to fully achieve desired lighting specifications. Final aiming means deviating
from designed aiming parameters to produce the best outcome on the playing surface. Typically, final aiming only requires
slight adjustments.
1.
Verify that all lights are correctly aimed according to the photometric or installation drawings.
2.
Measure light levels on the playing surface using a calibrated light meter. Unless otherwise noted, take readings at 3'
above ground, holding the meter out at arm's length as much as possible, thereby reducing the effect of the shadow
from your body.
N
otee:
Take horizontal readings by holding the meter face up, horizontal with the ground. Take Vertical footcandle readings by
facing the meter at an angle toward the vertical main or vertical end point. These vary based on venue and sport, but
basically refer to the typical locations for elevated main cameras, at the center lines directly off of the side and off of
the end of the playing surface.
Refer to specific project requirements or governing league regulations for more information. For reference, the NCAA lighting
best practices website has grid layouts by sport:
http://www.ncaa.com/news/ncaa/article/2013-11-21/ncaa-best-lighting-practices
3.
Review the light measurements and compare the data to project requirements or photometric drawings. If the light
measurements do not meet designed levels, final aiming is required.
There is no hard and fast rule on how to make final aiming adjustments as it is essentially an art form due to the
N
otee:
propagation and reflection properties of light. A bright spot is usually not caused by one individual luminaire but rather
the additive effect from several luminaires aimed in the same general vicinity.
4.
Note the areas of the playing surface that are the brightest and darkest and determine which luminaires are aimed
toward the bright areas and which are aimed near the darkest areas.
5.
Re-aim one or a few lights away from the bright areas and closer to the darker areas.
During final re-aiming, always minimize the number and size of aiming modifications. Make just one or a few small
adjustments and then re-check light levels. Making too many significant aiming changes may result in failure to meet
specified levels or introducing unwanted results such as glare.
6.
Re-measure light levels in areas where adjustments were made and compare new results to project specifications.
7 .
Repeat steps 5-6 as necessary to meet light level requirements.
Step 5 – Finishing Touches
To complete the installation, verify that all mounting, connection, and aiming work is finished.
Verify all electrical connections are tight and secured. The installer is responsible for the integrity of all connections.
●
●
Verify all bolts and screws are tightened and properly torqued.
●
●
Straighten up all cabling. Tie down all cables neatly. For all outdoor projects, use UV rated tye wraps and wire
●
●
management.
N
otee:
When power is turned on, the luminaires default to 100% on unless a different control signal is present.
Installation Instructions - All Field LED Luminaire
WARNING
EATON
MN507001EN
All Field Installation Manual rev 20170324
13