Start-up Guide
Nominal power. The general parameter setting procedure is
given on Page 2.
Range: 0... 9000 kW
When the motor data has been entered a warning appears.
It indicates that the motor parameters have been set, and
the ACS 600 is ready to start the motor identification
(ID magnetisation or ID Run).
Select the motor identification. The general parameter
setting procedure is given on Page 2.
The default value NO is suitable for most applications. It is applied in this
basic start-up procedure.
The ID Run (STANDARD or REDUCED) should be selected instead if:
• Operation point is near zero speed.
• Operation at torque range above the motor nominal torque within wide
speed range and without any pulse encoder (i.e. without any
measured speed feedback) is required.
See the Firmware Manual for the ID Run procedure.
Press the LOC/REM key to change to local control (L
shown on the first row).
Press the
magnetised at zero speed for 20 to 60 s. Two warnings are
displayed:
• The upper warning is displayed while the magnetisation
is on.
• The lower warning is displayed after the magnetisation is
completed.
4
START-UP PROCEDURE
4 – IDENTIFICATION MAGNETISATION
with Motor ID Run selection NO
to start the magnetisation. The motor is
1
->
0.0 rpm
99 START-UP DATA
09 MOTOR NOM POWER
[ ]
1
->
0.0 rpm
** WARNING **
ID MAGN REQ
1
->
0.0 rpm
99 START-UP DATA
10 MOTOR ID RUN
[NO]
1
L->
0.0 rpm
** WARNING **
ID MAGN
1
L->
0.0 rpm
** WARNING **
ID DONE
Standard Application Program
O
O
O
I
O