También para Siemens SINAMICS S120: Manual de instrucciones (20 páginas), Primeros pasos (32 páginas), Descripción breve (22 páginas), Manual (43 páginas), Instrucciones de instalación en armarios para aplicaciones de propulsión marina (28 páginas), Manual de aplicaciones (34 páginas), Manual de aplicaciones (46 páginas), Manual de instrucciones (22 páginas), Primeros pasos (32 páginas), Manual de instrucciones (21 páginas), Manual de ingeniería (30 páginas), Manual de puesta en servicio (20 páginas)

Siemens SINAMICS S120 Manual
5 Drives Configuration
5.4

Using a Freely Configurable Telegram

It is possible to configure a custom telegram to fit a specific application
requirement. The custom configuration can be accomplished by one of several
methods listed.
1. Using a standard telegram as a template and changing the configuration
manually.
2. Selecting the input and output data length and connecting the telegram words
in the communications window of the drive configuration.
3. Configuration by Script execution. A script can be written in Starter which
configures the telegram size and connections required. The script is then
executed in Starter configuring the drive.
Parameter r2067 displays the number of PZDs the controller detected to be part of
the telegram for the Drive Object. The Input and Output data length must match the
values calculated by the controller in r2067 of the specified Drive Object.
Figure 5-6 Number of Interconnected PZDs
NOTE
In order for the CU to correctly calculate parameter r2067, The last PZD of the
telegram must be interconnected.
For example if you are using Telegram 352 and change to Free-BICO telegram
(P922 =999) then the four freely configurable input value to the drive must be
terminated to "Dummy" parameters if they are not used for actual parameter
connection – such as torque limit or added speed.
Figure 5-7 Example of spare word holder script using p20110 (free blocks multiplier)
SINAMICS S: Speed control of a S120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP
Entry-ID: 92045369,
V4.0,
08/2018
25