Faults / Troubleshooting
LED
Designation
N°
Color
13
Yellow Loss of agent
14
Yellow Manual blocked
15
Yellow Not used
16
Yellow Automatic blocked
19
Yellow Sounders
20
Yellow Actuators
21
Yellow Fire controls
22
Yellow RT-Fault
23
Yellow RT-Alarm
24
Yellow Emergency hold
25
Red
Zone 1
26
Yellow Zone 1
27
Red
Zone 2
28
Yellow Zone 2
29
Red
Zone 3
30
Yellow Zone 3
28
Building Technologies
Fire Safety
State
Significance
Fixed
Short circuit
Slow
Break
Fast
Incorrect status
Fixed
Short circuit
Slow
Break
Fixed
24 V output fuse blown
Fixed
Key enabled more than 5 mn
Fixed
Short circuit
Slow
Break
Fixed
Short circuit
Slow
Break
Fixed
Short circuit
Slow
Break
Fixed
Short circuit
Slow
Break
Fast
Calibration error
Fixed
Short circuit
Slow
Break
Fast
Calibration error
Fast
Repeater error, digit display indicates the first repeater in
fault/missing condition
Fixed
Alarm < 15 s after reset
Fixed
Short circuit
Slow
Break
Fixed
Alarm < 15 s after reset
Fixed
Short circuit
Slow
Break
Fixed
Alarm < 15 s after reset
Fixed
Short circuit
Slow
Break
Monitored input 3
Monitored input 4
Monitored output 1
Monitored output 2
Monitored output 3
Monitored output 4
Monitored output 5
Detection line 1
Detection line 2
Detection line 3
A6V10257477_c_en_--