Siemens SITRANS LVL200E Manual de instrucciones - Página 20
Navegue en línea o descargue pdf Manual de instrucciones para Interruptor Siemens SITRANS LVL200E. Siemens SITRANS LVL200E 40 páginas. Vibrating switches
También para Siemens SITRANS LVL200E: Manual de instrucciones (44 páginas), Manual de instrucciones (16 páginas), Manual de instrucciones (40 páginas)
6 Set up
Function/Configuration
Signal lamp (1)
20
6 Set up
6.1 In general
The figures in brackets refer to the following illustrations.
In the basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and
adjustment elements:
Control lamp for indication of the switching condition (1)
l
DIL switch for mode adjustment - A/B (2)
l
DIL switch for sensitivity adjustment (3)
l
Note:
For test purposes, immerse the tuning fork of SITRANS LVL200E
always in liquids. Do not test the function of SITRANS LVL200E with
the hand. This can damage the sensor.
6.2 Adjustment elements
Fig. 12: Oscillator SWE60C - Contactless electronic switch
1
Signal lamp (LED)
2
DIL switch for mode adjustment
3
DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
Green = Output closed
l
Red = Output open
l
red (flashing) = failure
l
SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH
1
2
3