Siemens Sitrans WM100 Manual de instrucciones - Página 10

Navegue en línea o descargue pdf Manual de instrucciones para Interruptor Siemens Sitrans WM100. Siemens Sitrans WM100 16 páginas. Motion sensing switch
También para Siemens Sitrans WM100: Manual de instrucciones (22 páginas)

Siemens Sitrans WM100 Manual de instrucciones

WM100 Connection

Notes:
1.
Dry contacts shown in de-energized (alarm or shelf) state.
2.
WM100 is manufactured for either 115 or 230 V AC operation. Check
WM100 nameplate for applicable voltage. Correct voltage must be
supplied. Voltages lower than specified will result in an inoperative
condition. Voltages higher than specified will severely damage unit.
3.
For 5 second time delay and minimum 12 ppm range, connect jumper
across terminals 7 and 8. Without a jumper, the default is 10 second time
delay and minimum 6 ppm range.
Page 6
terminal circuit card
SITRANS WM100 – OPERATING INSTRUCTIONS
7ML19985MW01