FIRETRACE 800095-A Manual de instalación - Página 11

Navegue en línea o descargue pdf Manual de instalación para Unidad de control FIRETRACE 800095-A. FIRETRACE 800095-A 18 páginas. Dual pressure switch module with & without bypass

FIRETRACE 800095-A Manual de instalación
A continuity test using the continuity test function on a multi-meter can be performed on the Dual Pressure Switch Module to verify the configuration is
what is needed or to verify proper functionality of the pressure switches during servicing. Table 4 & Table 5 below specifies the state of each pressure
switch when the module is in either a pressurized or unpressurized state and when the bypass key switch is in the normal or bypass position for the
module with the bypass functionality.
1.
Note the configuration # the module has been set to
2.
Set the key switch position to "Normal"
3.
Connect the module to the detection circuit.
4.
Connect the leads to the first pressure switch being tested to a multi-meter set to the continuity test function.
a.
Reference Table 6 in Section 3.6 below for pinout details on the cable harness.
5.
Verify the first pressure switch is in the correct state when normal and unpressurized.
6.
Connect the multi-meter to the leads for the second pressure switch.
7.
Verify the second pressure switch is in the correct state when normal and unpressurized.
8.
Turn the key switch to the "Bypass" position.
9.
Verify the second pressure switch is in the correct state for when bypassed and unpressurized.
10. Connect the multi-meter to the leads of the first pressure switch.
11. Verify the first pressure switch is in the correct state for when bypassed and unpressurized.
12. Pressurize the detection network.
13. Verify the first pressure switch is in the correct state for when bypassed and pressurized.
14. Connect the multi-meter to the leads for the second pressure switch.
15. Verify the second pressure switch is in the correct state for when bypassed and pressurized.
16. Turn the key switch to the "Normal" position.
17. Verify the second pressure switch is in the correct state for when normal and pressurized.
18. Connect the multi-meter to the leads of the first pressure switch.
19. Verify the first pressure switch is in the correct state for when normal and pressurized.
Module
Config #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
DIOM 800095-A
Table 4 – Testing Reference | With Bypass
Key Switch
PS1
Position
(Unpressurized)
Normal
Closed
Bypass
Open
Normal
Closed
Bypass
Open
Normal
Open
Bypass
Closed
Normal
Open
Bypass
Closed
Normal
Closed
Bypass
Open
Normal
Closed
Bypass
Open
Normal
Open
Bypass
Closed
Normal
Open
Bypass
Closed
Normal
Closed
Bypass
Open
Normal
Closed
Bypass
Open
Normal
Open
Bypass
Closed
Normal
Open
Bypass
Closed
Normal
Closed
Bypass
Closed
Normal
Closed
PS2
PS1
(Unpressurized)
(Pressurized)
Closed
Open
Open
Open
Open
Open
Closed
Open
Open
Closed
Closed
Closed
Closed
Closed
Open
Closed
Closed
Open
Closed
Open
Open
Open
Open
Open
Open
Closed
Open
Closed
Closed
Closed
Closed
Closed
Closed
Open
Closed
Open
Open
Open
Open
Open
Open
Closed
Open
Closed
Closed
Closed
Closed
Closed
Closed
Open
Closed
Open
Open
Open
7
PS2
(Pressurized)
Open
Open
Closed
Closed
Closed
Closed
Open
Open
Open
Closed
Closed
Open
Closed
Open
Open
Closed
Open
Open
Closed
Closed
Closed
Closed
Open
Open
Open
Open
Closed
7/22/2022