CALEFFI 5495 SEP4 Instrucciones de instalación, puesta en marcha y mantenimiento - Página 2
Navegue en línea o descargue pdf Instrucciones de instalación, puesta en marcha y mantenimiento para Sistemas de filtración de agua CALEFFI 5495 SEP4. CALEFFI 5495 SEP4 4 páginas. 4-in-1 hydraulic, air, dirt and magnetic separator, ansi flanged
También para CALEFFI 5495 SEP4: Manual (16 páginas), Instrucciones de instalación, puesta en marcha y mantenimiento (4 páginas)
CAUTION: If the SEP4™ is not installed, commissioned and maintained
properly, according to the instructions contained in this manual, it may not
operate correctly and may endanger the user.
CAUTION: Make sure that all the connecting pipework is water tight.
CAUTION: When making the water connections, make sure that the hydronic
separator connecting pipework is not mechanically over-stressed. Over time
this could cause breakages, with consequent water losses which, in turn,
could cause harm to property and/or people.
CAUTION: Water temperatures higher than 100°F (38°C) can be dangerous.
During the installation, commissioning and maintenance of the hydronic
separator, take the necessary precautions to ensure that such temperatures
do not endanger people.
Technical specifications
Materials
Separator body:
Air vent body & shut-off and drain valve body:
Internal element:
Air vent seal:
Air vent float:
Magnet:
Magnet probe:
Performance
Suitable fluids:
Max. operating pressure:
Temperature range: - with insulation
Particle separation capacity:
Air separation efficiency:
Ferrous impurities separation efficiency:
Connections
Flanged:
Drain valve:
- connections 2"– 6":
- connection 8"– 14":
Thermo well tap (8 — 14" only):
- front center:
- inlet/outlet flanges:
Agency Approval
Series NA549_M is designed and built in accordance with Section VIII, Division
1 of the ASME Boiler and Pressure Vessel Code and tagged and registered with
the National Board of Boiler and Pressure Vessel Inspector, and CRN
registered, and stamped for 150 psi (10 bar) working pressure, with ASME U
stamp. 12"-14" is CRN pending, contact Caleffi.
water and non-hazardous glycol solutions up to 50%
- without insulation
100% removal to microbubble level
2"–14" ANSI B16.5 150 CLASS RF
2
epoxy resin coated steel body
300 series stainless steel
stainless steel
neodymium rare-earth
150 psi (10 bar)
32–220°F (0 – 105°C)
32–270°F (0 – 132°C)
up to 100% removal
1¼" NPT female
2" NPT female
¾" NPT female
½" NPT female
brass
VITON
brass
to 5 μm