aerauliqa CTRL-XWS Manual de instrucciones - Página 16

Navegue en línea o descargue pdf Manual de instrucciones para Controlador aerauliqa CTRL-XWS. aerauliqa CTRL-XWS 20 páginas.

aerauliqa CTRL-XWS Manual de instrucciones
4.2.4 MANUAL CONTROL
Press both
and
for about 5 seconds.
Four lines are shown on the display and then the % of the 0-10V regulation.
Release
and
(the led of the two buttons flash).
Press
to increase the regulation value.
Press
to decrease the regulation value.
The regulation % remains fixed at the desired point.
BACK TO THE AUTOMATIC MODE
Press both
and
for about 5 seconds.
Four lines are shown on the display and then the ambient temperature is displayed (the leds of the two buttons switch off).
4.2.5 SETTING OF THE CONSTANT DATA
+
-
Press both
and
for about 5 seconds.
Four lines are shown on the display and then the message CONF. is displayed.
Press
to scroll the setting menu.
Parameters:
P.r.o.b.
Cor.t. = temperature probe correction
SCAL = °C/°F Celsius or Fahrenheit degree
Air
SP.Lo = % of minimum speed
SP.Hi = % of the maximum speed
P.b. = proportional band of regulation
t.Lo.A = minimum temperature alarm
t.Hi.A = maximum temperature alarm
d.SE.t = temperature alarm relays hysteresis
AnEM.=0-1 activation/deactivation wind block
d.SE.r = on/off anemometer block hysteresis
t.Int. = 0-10V integration time
ImP. = number of pulses per revolution
Circ. = blade circumference
Unit = unit of measure 0=m/s 1=mph 2=km/h
Star = % minimum starting speed
4.3 ANEMOMETER BLOCK
Press twice
: the anemometer block setting ( SET = 3.0v) is displayed.
+
-
Press
or
to increase / decrease.
By activating in CONF. the function (ANEM.=1) and by connecting the anemometer, when the wind speed goes over the set level, the 0-10V signal is inhibited.
4.4 MEMORY OF THE REGISTERED TEMPERATURE (the values are retained even with the controller switched off)
+
Press
: the diagram is displayed followed by the maximum registered temperature value. Keeping
CLEA. is shown and the memory is cleared.
-
Press
: the diagram is displayed followed by the minimum registered temperature value. Keeping
CLEA. is shown and the memory is cleared.
4.5 SYSTEM RESET
Disconnect the controller from the main power supply.
Connect the controller to the main power supply and keep
+
Release
and wait for the reset.
Attention: Any setting will return to the default.
+
pressed until the word BOOT is displayed.
16
+
pressed for more than 3 seconds, the word
-
pressed for more than 3 seconds, the word