Measuring mode:
For limit value monitoring a limit value can be entered. This value is set in the menu item
„limit switch". The previously set parameters are taken into account (unit, parameter,
k-factor and the measuring range).
As default setting the limits are not active - Display - 2nd line: „OFF"
Alarm ON: Measurement for set delay time constantly greater than 1.0 • limit value
Alarm OFF: Measurement for set delay time constantly less than 0.95 • limit value
6.

Maintenance

The DPC200-R contains no wearing or consumable parts. Servicing is not required.
On request, Arthur Grillo GmbH offers an annual calibration with factory certificate.
For information, please contact:
Arthur Grillo GmbH
Am Sandbach 7
40878 Ratingen
7.

Warranty

Warranty and liability claims for personal and property damage are excluded if they are
caused by one or more of the following reasons:
Improper use of the device.
Improper installation, commissioning, operation and maintenance of the device.
Unauthorized modifications to the device beyond the intended use.
Disasters due to external influences and force majeure.
8.

Troubleshooting

Description
Display does not show
anything
Measurement stays zero
Measuring error
Error remains
Display shows:
14
Phone: +49 21 02 - 47 10 22
Fax:
Activity
Check electrical connection
Function test with a slight pressure increase in measu-
ring mode for differential pressure
Perform zeroing as described in chapter 4.5.
Contact manufacturer
!
The device is in the alarm state, see section 5.7