CVS Controls CVS1000L Manual del producto - Página 3

Navegue en línea o descargue pdf Manual del producto para Posicionadores de válvulas CVS Controls CVS1000L. CVS Controls CVS1000L 13 páginas. 1000l electro-pneumatic linear positioner

CVS Controls CVS1000L Manual del producto

Specification

CATEGORY
Input Signal
Impedance
Supply Pressure
Stroke
Air Connection
Gauge Connection
Conduit Entry
Explosion Proof
Protection
Ambient Operating
Temperature
Linearity
Hysteresis
Sensitivity
Repeatability
Air Consumption
Flow Capacity
Material
Weight
* 1: For 1/2 Split Control, it can be applied by adjusting zero and span.
* 2: For inquiries regarding strokes under 10mm or above 150mm, please contact CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
YT - 1000L
Single
4 ~ 20mA DC *1
250±15Ω
1.4 ~ 7.0kgf/cm
(20 ~ 100psi)
2
10 ~ 150mm *2
1/4' NPT
1/8" NPT
1/2" NPT
CSA: Class 1, Zone 1, Group IIB, T5
IP66
-40 ~ 60°C
±1.0% F.S
1.0% F.S
±0.2% F.S
±0.5% F.S
3LPM (Sup=1.4kgf/cm
80LPM (Sup=1.4kgf/cm
Aluminum Diecasting
2.7 kg (6.1 lbs)
3
CVS Controls Ltd.
Double
±0.5% F.S
, 20psi)
2
, 20psi)
2
CVS Controls Ltd.
Process Management
And Instrumentation