MOUNTING
When the detector is mounted on a ceiling, it is necessary to follow the requirements of Rules СП5.13130.2009, in
particular Table 13.3:
Height
Below 3.5 m
3.5 ÷ 6 m
6 ÷ 10 m
10 ÷ 12 m
If cannot be installed on a ceiling, the DIP-34PA-03 can be mounted on wire ropes as well as on a wall, a column, or any
other structural. Installing point-type detectors on walls please follow the instructions of Appendix "П" of Rules
СП5.13130.2009.
Figure 2 shows two possible ways of attaching the detector. To attach the detector to a solid surface (variant A) use the
mounting base provided (see also the drilling pattern in Figure 3, at the left). Otherwise, a separately purchased mounting
kit MK-2 can be used to build the detector into a suspended ceiling (variant B). The size of the mounting hole is shown in
Figure 3, at the right.
AT T ENT IO N
To install the detector on the base plate, align the guide on the detector with the short guide of the base plate.
Then turn the detector clockwise until the detector guide is aligned with guide 3 as shown in Figure 2 (А).
INDICATION
Light Emitter Behavior
Flashes once per 8 seconds
Two flashes once per 8 seconds
Three flashes once per 8 seconds
Three flashes (flickering) once per 2 seconds
Four flashes once per second
Average Area Monitored by
a Single Detector
Up to 85 sq.meters
Up to 70 sq.meters
Up to 65 sq.meters
Up to 55 sq.meters
Figure 2
Figure 3. Drilling Pattern
Norm
Fire Alarm or Test
Service Required or Trouble
Indication of undefined (factory set) address in an addressable alarm
loop
Being connected to a non-addressable alarm loop or dc power supply;
or the DIP-34PA-03 is waiting for assigning an address
Distance
Between Detectors
9.0 meters
8.5 meters
8.0 meters
7.5 meters
1:
DIP-34PA-03 Detector
2:
Light Emitter
3:
Alignment Guide
4:
Mark and Bar, OPEN HERE
5:
Base Plate
6:
MK-2 Suspended Ceiling Mounting Kit
(ordered separately)
Figure 3 shows the drilling pattern to
install the detector for the variant A and
the diameter of the mounting hole in the
suspended ceiling for the variant B.
Detector Status/Condition
Between Detector and Wall
4.5 meters
4.0 meters
4.0 meters
3.5 meters