DESCRIPTION AND OPERATION
1.1 Purpose
1.1.1 ShPS-12, ShPS-12 mod.01, ShPS-12 mod.02, ShPS-12 mod.10, ShPS-12 mod.11, ShPS-
12 mod.12 (hereinafter referred to as ShPS-12) are meant to provide power supply for groups of installed fire
control equipment, manual call points, alarm and control panels (modules) and other fire protection equipment
requiring 12V/DC.
ShPS-12 mod.01 boxes differ from ShPS-12 boxes by a transparent window door; ShPS-12 mod.02 boxes
differ from ShPS-12 boxes by IP54 ingress protection rating.
ShPS-12 mod.11 differs from ShPS-12 mod.10 by a transparent window door; ShPS-12 mod.12 differs from
ShPS-12 mod.10 by IP54 ingress protection rating.
ShPS-12 mod.10, ShPS-12 mod.11, ShPS-12 mod.12 differ from ShPS-12, ShPS-12 mod.01, ShPS-12 mod.02
by two separate RS-485 interface lines (instead of one line, see Clause 1.2.9).
An ShPS-12 box can accommodate the following Orion ISS devices: Signal-10, Signal-20P, S2000-4,
S2000-KDL, S2000-KPB, S2000-SP1, S2000-PI, S2000-KDL-2I, Rupor mod.02, S2000-PGE, S2000-PGE
mod.01, S2000-Ethernet, S2000-RPI and other devices mountable on 35 mm top-hat DIN rail in accordance
with GOST R MEK 60715-2003.
1.1.2 ShPS-12 is designed for 24/7 continuous operation with intended output parameters, automatic
monitoring and charging of sealed backup batteries. ShPS-12 provides disconnecting backup batteries from
load circuits to avoid unacceptable discharge. ShPS-12 provides protection against open / short failures for the
battery connection circuit.
1.1.3 ShPS-12 provides visual and audible indication of the following: mains supply status (availability,
high / low voltage), backup battery status, missed batteries, disconnection of low batteries, output short
circuit / overcurrent, charger faults, output overvoltage, status of communications over the RS-485 interface
bus.
1.1.4 Being powered by mains and by batteries, ShPS-12 provides overvoltage and short-circuit protection
for 12V/DC outputs, with the output voltage being restored automatically after repairing an output short-circuit
fault.
1.1.5 ShPS-12 shall be installed in locations protected from atmospheric precipitation and mechanical
damage. ShPS-12 boxes are not designed for operating in locations where they can be exposed to explosion
and / or flammable hazards.
1.1.6 ShPS-12 is classed as recoverable and periodically serviced equipment.
1.2 Specifications
No.
1.2.1
Power Inputs
1.2.2
Primary power supply: The mains utility AC power 50/60 Hz
Backup power supply: Bolid series batteries AB 1207 (the type С or М)* or
1.2.3
similar
1.2.4
Output voltage: while powered by
1.2.5
Rated / maximum load current
1.2.6
Outputs for powering devices consuming 12 V and installed within ShPS-12
1.2.7
Maximum current per a single output 12V/dc
1.2.8
Outputs for connecting RS-485 interface lines installed within ShPS-12
For ShPS-12, ShPS-12 mod.01, ShPS-12 mod.02:
RS-485 port for connecting external devices over the RS-485 interface
1.2.9
For ShPS-12 mod.10, ShPS-12 mod.11, ShPS-12 mod.12:
Separate RS-485 ports for connecting external devices over the RS-485
interface
1.2.10
Capacity of non-volatile event log
1.2.11
Maximum power / current consumed from the mains
1.2.12
Current consumed from the batteries by the ShPS-12 itself
SHPS-12 FIRE EQUIPMENT MOUNT BOXES
WITH BACKUP BATTERY POWER SUPPLIES
ShPS-12 mod.01
ShPS-12 mod.11
Operations Manual
Parameter
ShPS-12 mod.02
ShPS-12 mod.12
Value
2
150...253 V
12 V, 17 Ah (2 batteries)
mains (13.6±0.6) V
batteries (13.5...9.5) V
3 A / 3.5 A **
7
0.65 A
7
1
2
95 events
120 V·A / 0.8 A
40 mA max
Table 1
1