Baumer PAC50S Manuel d'utilisation - Page 24
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Baumer PAC50S. Baumer PAC50S 44 pages.
9
|
Commissioning
9.6
Media calibration
INFO
This task can be done either using the FlexProgram or via IO-Link (e.g. BSS). The following ex-
ample shows calibration with FlexProgram.
Media calibration for the different ranges is by calculating the temperature compensation after 3
measuring operations.
Condition:
ð The sensor is connected to a PC with software FlexProgram installed.
ð The sensor is switched on.
ð Calibration is performed in a controlled environment.
Instruction:
a) Open software FlexProgram on the PC.
b) Open setting PAC50 in the left column.
c) Click on icon
d) Click on button
ü
Dialog window opens.
e) Select the calibration range from the Drop-Down menu
f) Start the measuring operation by clicking on button Measure.
Repeat the measuring operation in the same medium at 3 different temperatures
NOTICE! . In each measuring operation, the sensor tip must be immersed in the
medium for at least 1 minute.
g) Calculate the media temperature compensation by clicking on button Calculate.
Result:
ü
Calibration completed.
24
Measuring
(Online).
Calibrate Media
below the visualization.
Operating Manual
Select
range.
PAC50H/S | V1
Baumer