PRESS THE
SETTING
Valve
Trial for
MODE
Delay On*
Ignition
OPTIONS
No Valve
15 Sec
PRESS THE
0 Sec
30 Sec
3 Sec
45 Sec
10 Sec
BUTTONS
15 Sec
TO
30 Sec
CHANGE
SETTINGS
60 Sec
2 min
Shaded box = default setting; CAD Ohms Max default is application dependent.
* When selecting "No" valve during initial startup, "Valve Delay On" will be set to "No Valve" and "Motor
Delay Off" will be set to "0 Sec".
• Valve Delay On: Time period motor and ignitor are on
prior to Trial for Ignition. This setting is often referred to as
"pre-purge". Note: If flame is sensed during valve delay on,
control will lockout immediately.
• Trial for Ignition: Flame-establishing period during ignition.
Note: Do not use 45 TFI for burners larger than 3GPH.
• Motor Delay Off: Time period the motor is on after the Call
for Heat is satisfied to allow for evacuation of combustion
gases. This setting is often referred to as "post-purge". A
call for heat during Motor Delay Off will result in a recycle.
Note: If Valve Delay On is set to "0 Seconds" or "No Valve",
Motor Delay Off can only be set to "0 Seconds".
• Flame Stabilize: The time period after Trial for Ignition that
the ignitor remains on to stabilize flame.
• CAD Ohms Max: The maximum Ohms range that the con-
trol will allow the burner to operate.
• Ignition Type
Interrupted: Spark is turned off after Flame Stabilization
period.
Smart Ignition: If flame is lost at any time after the Flame
Stabilization period, the control will recycle (60 - 65 sec-
onds). Following this recycle, the control will operate in
Intermittent Duty mode (ignition on throughout the call for
heat) for ten heat cycles. Following these ten cycles, the
control will revert back to Interrupted Duty and will remain
in Interrupted Duty until another recycle event occurs.
• TT Jumpered: Allows TT to be "jumpered" by software
program.
Carlin Combustion Technology, Inc.
A V A I L A B L E
BUTTON TO VIEW DIFFERENT SETTING MODES
Motor
Flame
CAD Ohms
Delay Off*
Stabilize
Max
0 Sec
Off
Carlin 3300
10 Sec
5 Sec
Other 5300
15 Sec
10 Sec
30 Sec
15 Sec
2 min
30 Sec
5 min
45 Sec
15 min
Setup Menu Definitions
S E T T I N G S
Ignition
TT
Vent
Type
Jumpered
Input
Interrupted
Yes
Not Used
Smart Ign
No
Intake
Exhaust
• Vent Input: Applicable only to applications equipped with
a com¬bustion air proving switch (Intake) or a blocked vent
switch (Exhaust): The Intake setting has a 10 second delay
before shut¬ting down in the event the air intake is blocked.
The burner will recycle (subject to the Allowed Recycles
setting). The Exhaust setting allows for a 30 second delay
after flame is proven at each burner start up. If the vent is
blocked at the conclusion of the 30 second delay, the burn-
er will shut down and lock-out immediately. If the vent is not
blocked at start-up, but becomes blocked sometime after
the 30 delay, the burner will shut down immediately, but will
be allowed to recycle (subject to the Allowed Recycles set-
ting). Note: The above assumes the blocked vent switch is
not equipped with its own lock-out feature.
• Allowed Recycles: Number of Recycles allowed during a
single Call for Heat prior to lockout.
• Clear Fault History: Allows all prior burner fault conditions
stored in control to be cleared.
• Restore Factory Defaults: Allows all factory defaults to
be restored in control (refer to settings shaded in gray in
the table above). Will reset and reboot control and require
answer to "solenoid valve" question at startup.
Per UL requirements, the control will not turn
on if the cad cell senses flame (light) during the
self-test. If the cad cell sees flame, the control
will remain in self-test mode until the cad cell no
longer senses flame.
5
Restore
Allowed
Clear Fault
Factory
Recycles
History
Defaults
None
Yes
Yes
3
No
No
MN70200B 060217