Operating Sequence
With power to the control and all manual oil line valves open,
set thermostat (and limit) to call for heat. NOTE: The ther-
mostat circuit must be closed and power must be coming to
black wire from limit circuit.
Pre-Ignition
Following a 3 sec Pre-Ignition, the control advances to Valve
Delay On –
Valve Delay On
During Valve Delay On, motor starts. After set timing, valve
opens and the control advances to Trial for Ignition when the
countdown clock expires. NOTE: For the Valve Delay to oper-
ate, the burner must be equipped with a solenoid valve that is
wired to the violet terminal.
Trial for Ign
During Trial for Ignition, the CAD cell must sense flame or
the control will go into lockout. When flame is detected, the
screen will briefly display "Flame Detected" and then return
to the "Trial for Ign". When the countdown timer expires, the
control advances to Flame Stabilization
NOTE: Push View Ohms button anytime during burner opera-
tion to view the CAD Ohms reading.
Flame Stabilize
When the Flame Stabilize timer expires, the ignitor will turn
off and the burner will continue to fire until the Call for Heat
ends or the limit string opens. The screen will display "Burner
Running". Note: If Smart Ignition is selected in the Setup
Menu, the screen will alternate between "Burner Running"
and "Smart Ign Active" at any time the ignitor is running in
intermittent mode.
Burner Running
When the Call for Heat ends (or a limit control interrupts the
burner circuit), the oil valve (if installed) will turn off within
2 seconds. The motor remains on for the Motor Delay Off
period. When the Motor Delay Off timer expires, the control
returns to Standby mode awaiting the next call for heat.
Motor Delay Off
Standby
No Call for Heat
Carlin Combustion Technology, Inc.
X X Sec
X X Sec
X X Sec
X X Sec
5 9 Sec
X X Sec
5 9 Sec
Pump Prime (Bleeding)
The 70200 control is equipped with a 120 second pump
prime feature. To enter Pump Prime, there must be a Call for
Heat. NOTE: If a flame is present, the control will not enter
Pump Prime mode.
To bleed the oil line, with Limit icon on, push and hold red
Reset button for 10 seconds. The display will read Pump
Prime.
The motor, valve and ignitor remain on for up to 2 minutes
while in Pump Prime mode. To end Pump Prime mode, press
the red Reset button. NOTE: If flame is sensed, Pump Prime
mode ends in 5 sec.
Pump prime cannot be entered when the control is in Lockout
or Latch-up.
Fault History
The 70200 stores information from the last 32 cycles in which
a fault condition occurred. To Enter the Fault History , simul-
taneously press and hold the
The display below will appear –
View 13 Faults
To Exit Hold
E
Press the
button to scroll through the history of fault
conditions. Fault 1 is the most recent cycle in which a fault
occurred. To view faults experienced in earlier run cycles,
E
continue to press the
2 followed by Fault 3, etc.
Fault 1 Details
View Fault 2
To view the details of any fault (ex. Fault 1 in the screen
H
above), press the
button to see the Fault Message.
Fault 1 Message
No Flame Check Vlv
H
Press the
button again to determine how many cycles ago
the fault occurred.
Fault 1
X X X X cycles ago
H
Press the
button again to determine if the fault resulted in a
lockout or a recycle.
Fault 1 Result
Lockout
H
Press the
button again to examine the Ohms at the time of
the fault.
Fault 1
CAD X X X X X O h m s
6
H
E
and
buttons for 2 seconds.
button. The control will display Fault
MN70200B 060217