Oil Cooling Capacity
Fan Speed
Ambient Air Temperature
KH51ZZ181
KH51ZZ182
KH51KK183
KH51KK183
*Maximum Number of Compressors Based on Oil Cooler Pressure Drop of Less Than 6 PSID (.41 bar)
3.8

Oil Cooler Selection

Oil coolers are required for 06T compressors where the oil
temperature can exceed 190°F (88°C) and for 05T com-
pressors where it can exceed 180°F (82°C). The CARWIN
selection software should be used to determine operating
conditions where this will occur. For initial reference, the op-
erating envelopes in Section 2.1 may be used as an initial
reference.
The oil cooler should be sized based on an oil flow rate of
approximately 2 gallons per minute (7.6 liters/minute) per
compressor. However, it should be noted that the actual oil
flow rate will vary based on the specific operating condition.
Oil cooler loads may be obtained from the CARWIN selec-
tion software. With an oil cooler, the maximum oil tempera-
ture leaving the oil cooler is 170°F (77°C). Systems using
external oil coolers also require controls that prevent the oil
temperature from dropping below 80°F (27°C).
Acceptable means of control are fan cycling or oil cooler by-
pass or mixing valves. Mixing valves are recommended for
any oil coolers that are integrated into the system condens-
er coil. For direct expansion oil coolers rejecting heat into
the refrigeration circuit caution must be taken to ensure that
the return gas temperature is within operating guidelines.
3.9

Oil Filter

Carlyle screw compressors are designed with rolling ele-
ment bearings to provide exceptional life. Oil to the bearings
must pass through a 3 micron filter which is required on all
Carlyle screw compressor systems.
NOTE: Use of the Carlyle 3 micron filter element is required.
Use of a non-Carlyle- approved filter element will void com-
pressor warranty. The use of a second redundant filter in
parallel is recommended to allow for servicing of one filter
while the other maintains the operability of the equipment.
95°F
Maximum 2
32.1
compressors
Maximum 3
69.1
compressors
Maximum 4
102.6
compressors
Maximum 5
134.1
compressors
kBtu/hr
60Hz
100°F
105°F
110°F
30.6
29.9
27.6
65.7
62.4
59.1
97.7
92.8
87.9
127.7
121.3
114.9
If more than five compressors are fed by the oil system,
three parallel oil filter elements (2 for operation, 1 for redun-
dancy) should be used to avoid excessive pressure drop
through the filter elements. The oil filter should be located
downstream from any oil coolers, as close to the compres-
sors as possible.
Oil Filter Pressure Drop Protection:
LonCEM protection
Carlyle recommends maximum allowable pressure drop
across the oil filters of 45psid (3bar). Compressors should
be shutdown above this limit. Carlyle also recommends an
alert (shutdown not required) when the pressure drop rises
above 25psid (~1.5bar).

3.10 Oil Sump Heaters

The heater must be energized during the system off cycle if
used. This is required in all air conditioning systems and is
recommended in refrigeration systems to keep refrigerant
out of the oil sump during compressor off cycles. Carlyle
typically recommends flexible heaters that are applied on
the outside of the oil separator shells. Carlyle recommends
500W heaters for shells 12 inches and smaller and 100W
for heaters larger than 12 inches. Direct immersion heaters
may also be used. Carlyle advises caution with these im-
mersion heaters, localized temperatures surrounding the
heater element should not create issues with the lubricant.

3.11 Oil Sight Glass

A sightglass is required in the main oil line. The sightglass
must be located after the oil filters and just prior to the first
compressor on a multiple compressor rack. To aid service
personnel in verifying oil flow to any given compressor
Carlyle recommends a sightglass be placed in each branch
oil line between the compressor and its oil solenoid.
kW/hr
50Hz
35°C
38°C
41°C
9.4
9.4
8.4
18.7
17.8
16.9
27.8
26.5
25.2
26.2
34.4
32.7
— or —
43°C
8.0
16.0
23.9
30.1