4.0 Refrigerant Management System
4.1 Suction and Interstage Piping
The suction and interstage manifolds should be piped in
such a way that liquid cannot gravity drain into any compres-
sor. Carlyle recommends that the manifold be located below
the compressor body. An inverted trap must be used com-
ing off the top of the suction header if it is above the com-
pressor body.
NOTE: If suction or interstage piping is to be located above the compressor the recommendations in the figure below also
apply.
Mechanical subcooling via interstage manifolds are com-
monly applied with parallel 05T/06T rack designs. The gas
exiting the subcooler is used to provide additional motor
cooling in 06T models. This design reduces the amount of
liquid injection required for motor cooling. The manifold acts
SUCTION AND INTERSTAGE HEADER SCHEMATIC
(HEADER LOCATED ABOVE COMPRESSOR INLET)
SUCTION AND INTERSTAGE HEADER SCHEMATIC
(HEADER LOCATED BELOW COMPRESSOR INLET)
Steel refrigerant piping is not recommended for use with
05T/06T screw compressor applications. The contaminants
associated with the steel pipe will overload the 3 micron fil-
ters used in the oil system increasing the chances of oil re-
lated compressor failures.
45°
1
/
" gap
8
(3mm)
to efficiently distribute refrigerant gas to each compressor.
Interstage headers should be designed similar to suction
line manifolds.
13