– When the internal cooling air supply stops for more than 20
minutes, remove the burner and seal the seal plate. Prevent burner
damage.
– External cooling air supply for a long time will cause damage to the
sealing plate.
– To adjust the firing burner, loosen the corresponding fixing bolt
and lock it again after the adjustment is completed
– Do not remove the metal gas hose or locking device when the gas
is not completely shut down
4.1 Burner data sheet
Burner
Burner
Model
Input Gas
Number
MW
12L3000
0.6-3.0
12L6000
1.5-6.0
4.2 Installation of the burner
1. Preparation of the burner bracket
Before installing bracket, check all ruler positions, which should be in zero
position; otherwise, loosen the fixing bolt first, and return ruler to zero. As
shown in figure 2, adjust the bracket so that the four fixing bolts are in the middle
position of the chute to ensure that the bracket can move forward, backward,
left and right directions.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – FFA12 Burner Operation Manual
Attention!
Fuel Pressure
Fuel Flow
Required
(L/H)
@Burner (bar)
min
max
min
60
300
0.5
125
600
0.5
4
Atomizing air flow
3
/H)
(NM
max
Recommended value
3
30
3
60
Atomizing air
pressure
(bar)
min
max
1
3.5
1
3.5