Atkinson Electronics GSCM Instructions d'utilisation et d'installation - Page 7

Parcourez en ligne ou téléchargez le pdf Instructions d'utilisation et d'installation pour {nom_de_la_catégorie} Atkinson Electronics GSCM. Atkinson Electronics GSCM 16 pages. Generator start control module
Également pour Atkinson Electronics GSCM : Manuel (16 pages)

Atkinson Electronics GSCM Instructions d'utilisation et d'installation
GENERATOR START CONTROL MODULE
GENERATOR EMERGENCY SHUTDOWN WITH THE GSCM
The GSCM Generator Start Controller is NOT AN EMERGENCY SHUTDOWN DEVICE!! Shorting the reset terminals 7 and 8
terminates the current GSCM cycle (see Section 5). If the manual start signal is removed the generator will go through a normal
shutdown which may include running for up to two minutes in a "load removed" cool-down cycle. Also shorting reset terminals
7 and 8 will shutdown the generator in a normal sequence including the cool-down cycle. If the generator has started but is in
the "load delay period", applying a reset to terminals 7 and 8 will shutdown the generator immediately.
A RECOMMENDED EMERGENCY SHUTDOWN SOLUTION is to install a separate "Kill" switch and label it as such. The
recommended wiring is shown on page-2 of these instructions and also in Application 1. Disconnecting the power to the GSCM
module will force the relays to open. This will shutdown generators that require a maintained run signal from K3 (ignition) relay.
However this also prevents the K4 (shutdown) relay from closing to shutdown those generators requiring a momentary stop signal.
Using a double pole "Kill" switch and wiring the second pole in parallel with the K4 (shutdown) relay terminals will force the
generator to stop in an emergency situation such as a fuel spill.
LED DESCRIPTION (WHAT THEY MEAN)
OPERATION LEDS:
1.
continuous = manual start signal received; one blink every 5 seconds = ready to receive a command;
Start:
slow blink = auto start mode operation; fast blink = 60 second delay after reset, before "ready" mode
2.
Generator Hz Shutdown:
3.
Emergency Shutdown:
4.
Max. Crank Shutdown:
ADJUSTMENT & TIMING LEDS:
1.
0-60 Second Crank Delay:
2.
0-60 Second Maximum Crank:
3.
0-60 Second Load Delay:
4.
0-120 Second Load Pre-Off:
5.
Battery Charge Cut-In (x12):
6.
Battery Charge Cut-Out (x12):
7.
15-75Hz Under Hz Shutdown:
8.
15-75Hz Over Hz Shutdown:
9.
15-75Hz Run/Crank Off:
10. 0-1 Hour 30 Day Exercise:
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
fast blink = over speed; slow blink = under speed
continuous = start function disabled, AC Hz detected before starting
fast blink = high temperature; slow blink = low oil pressure
fast blink = max. 4 crank attempts exceeded; slow blink = 12 hour max. runtime exceeded
continuous = adjustment selection;
blinking = entered crank delay period while glow plug relay K1 energized
continuous = adjustment selection;
blinking = rest period after unsuccessful cranking attempt
continuous = adjustment selection;
blinking = generator running, delay period before load transfer
continuous = adjustment selection;
blinking = load disconnected, cool down period before shutdown
continuous = adjustment selection;
blinking = battery voltage lower than cut-in point, during 5 minute delay
continuous = adjustment selection;
blinking = battery voltage greater than cut-out point, during 10 minute delay
continuous = adjustment selection;
blinking = generator Hz (under speed) less than trip point, during 10 second delay
continuous = adjustment selection;
blinking = generator Hz (over speed) greater than trip point, during 10 second delay
continuous = adjustment selection; no blinking condition
continuous = adjustment selection;
one blink every minute = 30 day exercise option activated;
fast blink = 60 second warning before 30 day exercise generator starting
Distributed by:
GSCM
SECTION - 6
SECTION - 7
REV 8/06