Networked General Purpose Adapter (WGA100)
®
4
Wiring
Line voltage wiring connects to the electrical supply circuit.
The Black (Hot) flying lead and the Red (Switched Load) flying
lead are 14AWG. The White (Neutral) flying lead is 18AWG.
Low voltage 22AWG flying leads provide connections to supply
low voltage power and carry control and monitoring signals to
and from low voltage input and output devices such as a fan
controller, humidity sensor, setback thermostat, etc.
After joining the wireless network, the control signals from the
low voltage devices pass through the WGA100 and are sent
wirelessly to Daintree Networked. Depending on the zone and
device configuration in the DCS, wireless signals from the WAC
to the WGA100 determine the operation of the devices
connected to it.
Figure 3: Wiring Identification
Reducing noise on low voltage (0-10V) wiring
• Keep wiring as short as practical
• Keep signal lines separate from mains voltage lines.
• Reduce the area created by the signal lines and
the GND return (i.e., keep them close together).
• If possible twist the signal line with the GND return.
Figure 4: Switched Line Voltage Load Relay
(Binary Output, DIP Switch 1 On)
Risk of electrical shock. Disconnect all power before installation and
during servicing. Do not open WGA100 enclosure; no user-serviceable
parts inside. All installation and maintenance of line voltage equipment
must be performed by a qualified electrician. The WGA100 must be
installed in accordance with all local, state, and national electrical codes
or Canadian Electrical Code, Part 1, and in a manner acceptable to the
local authority having jurisdiction. Wiring connectors are not supplied.
UL recognized wiring connectors must be used in the installation.
3