[Speci cations]
■General Speci cations
Ambient temperature/humidity for use
Ambient temperature/humidity for storage
Atmosphere for use
Altitude of use *
2
Pollution level *
3
*1 When expanding with 1 to 2 extension units: 0 - 55°C
When expanding with 3 to 10 extension units: 0 - 50°C
When expanding with 11 or more extension units: 0 - 45°C
*2 Do not use or store the AnyWireASLINK device in an environment pressurized equal to
or higher than the atmospheric pressure at the altitude of 0m. Doing so could cause a
malfunction.
*3 Index that indicates the occurrence of conductive material in the environment where the
device is used.
Contamination level 2 indicates that only non-conductive contamination occurs.
However, incidental condensation could create temporary conductivity in this
environment.
■Transmission speci cations
Power supply
Voltage 24V DC +15% to -10% (21.6 to 27.6V DC)
voltage for use
Ripple of 0.5Vp-p max.
Transmission method
DC power supply superimposed total frame/cyclic method
Synchronization method
Frame/bit synchronization method
Transmission procedure
Dedicated protocol
Connection mode
Bus type (Multi-drop method, T-branch method, Tree branch method)
Number of connection points
512 max. (IN: 256, OUT: 256)
Number of units connected
Up to 128 units
RAS feature
Transmission line disconnection, transmission line
short-circuit, transmission power supply reduction
detection ID redundancy, ID not set
■Individual speci cations
Number of occupied points
Response time *
4
Consumption current
Mass
Protective structure
Ambient illuminance for use
*4: Time from when ON or OFF is detected until the transmission signal is transmitted.
For the data to change, this time + 1 transmission cycle time is required.
[Detection distance]
■Fiber head (AnyWire dedicated head)
Type
Transmission type
AFT-4 (M4, R30)
Transmission type
AFT-1 (M3, R20)
Transmission type
AFT-2 (M3, R25)
Transmission type
AFT-1-1 (100°C, M3, R20)
* "Diagnosis" refers to the amplifier's monitoring and notification functions, such as
"sensor level reduction" and "transmission signal level reduction."
0 - 55°C *
, 10 - 90%RH (No condensation)
1
-25 - 75°C, 10 - 90%RH (No condensation)
No corrosive gas
0 to 2000m
2 or less
One-point input
1 - 2 cycles
24V-0V
25mA
DP-DN
1.9mA
21g (Base unit)
17g (Extension unit)
IP40
Incandescent lamp
3000 lx or less
Sunlight
10000 lx or less
Detection distance (mm)
Model name
With
diagnosis*
410
160
300
170
[Outside Dimensions]
■LA-F1011 (Base unit)
■Transmission line
■LB-F1011 (Extension unit)
Without
diagnosis*
600
210
420
240
-L*F1011 10/11-
10
Φ1.1
Φ4.1
Four cores, AWG24
Cable length: Approx. 200mm
10
Unit: mm
36.7
32
7
36.7
32
7