Modbus Register
6. Modbus Register
Register
Address
Type
40002
Single Write
Command
40003
Multiple Read
Starter
status
40004
Multiple Read
Trip Code
1
40005
Multiple Read
Motor
current
40006
Multiple Read
Motor
temperature
40007
Multiple Read
Product Type
and Version
40008
Multiple Read
Serial
Protocol
Version
2
40009
~
Single Write
Parameter
and Multiple
management Read
Description
1 = Start
2 = Stop
3 = Reset
4 = Quick stop (coast to stop)
5 = Forced communication trip
Bit
Description
0 to 3
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including
Temperature check)
6 = Tripped
7 = Program mode
8 = Jog forward
9 = Jog reverse
4
1 = Positive phase sequence (only valid if bit
6 = 1). Always = 0
5
1 = Current exceeds FLC
6
0 = Uninitialised
1 = Initialised
7
Always = 0
See Trip Code table.
Average 3 phase motor current (A)
Motor temperature (thermal model)
Bit
Description
0 to 2
Product parameter list version
3 to 7
1= MCD 3000
4= MCD 200
7 = MCD 500
Parameter 1-A (Motor FLC) to:
•
MCD 500 Par. 20-6 (Pedestal Detect)
•
MCD 3000 Par. 60 (Min Run Frequency)
MG.17.F5.02 - VLT® is a registered Danfoss trademark
MCD Modbus Module Instructions