Dantherm CDP 50 Instructions relatives au kit de service - Page 5
Parcourez en ligne ou téléchargez le pdf Instructions relatives au kit de service pour {nom_de_la_catégorie} Dantherm CDP 50. Dantherm CDP 50 12 pages. Replacing rh/t sensor
Également pour Dantherm CDP 50 : Manuel d'installation rapide (14 pages), Installation rapide (20 pages), Manuel (6 pages)
11.
Mount the humidity sensor on the bracket with
PPI filter and two cable binders as shown.
12.
Run a full test of the unit with the latest software version.
(Instructions on how to download and install latest software version is found on next page)
13.
Remount the front and make sure the sensor is
visible through the grille.
Instructions
Note: the white surface and hole in the sensor must be
facing front.
EN
5