Contech VortSentry HS36 Manuel d'entretien - Page 3

Parcourez en ligne ou téléchargez le pdf Manuel d'entretien pour {nom_de_la_catégorie} Contech VortSentry HS36. Contech VortSentry HS36 3 pages. Stormwater treatment system

VortSentry HS Model:
Water depth
Date
to shipment
1
1.
The water depth to sediment is determined by taking two measurements with a stadia rod: one measurement from the manhole opening to the
top of the sediment pile and the other from the manhole opening to the water surface. If the difference between these measurements is less
than the distance given in Table 1, the system should be cleaned out. Note: To avoid underestimating the volume of sediment in the chamber, the
measuring device must be carefully lowered to the top of the sediment pile.
2.
For optimum performance, the system should be cleaned out when the floating hydrocarbon layer accumulates to an appreciable thickness. In
the event of an oil spill, the system should be cleaned immediately.
VortSentry HS Inspection & Maintenance Log
Describe
Floatable layer
maintenance
thickness
2
performed
Location:
Maintenance
Personnel
Comments