Data Aire dap4 touch Manuel de démarrage rapide - Page 6

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Data Aire dap4 touch. Data Aire dap4 touch 9 pages. Modbus tcp/ip protocol integration
Également pour Data Aire dap4 touch : Manuel de l'utilisateur (8 pages), Instructions d'installation (2 pages), Manuel du protocole (13 pages)

Data Aire dap4 touch Manuel de démarrage rapide
This is a view only menu detailing the processor version and requires the service level password to enter.
Menu allows programming of available protocols. Typically this menu is factory set.
Requires a service level password for programming
Allows calibration of the installed unit sensors if required
Requires a service level password for programming
Allows the unit components to run manually. Used for diagnostic of individual components within the unit.
Requires a service level password for programming
Menu J is for setting the control to the type equipment and options ordered. This includes compressor type and quan-
tity, blower type, blower running speed or mode, chilled water valve type, Energy Saver, humidifier, reheat and other
additional features. This requires the Factory Level password and entry should be limited to Data Aire factory and
service personnel.
Menu K is for setting the control alarms, limits, alarm enunciation mode, configure optional and custom alarms.
Firestat alarm will shut unit down, its limit is programmed at 150°F as default value. (150 Deg F is default in software
version 1.25 or later. 100 Deg F is default value in older software version.) Change this limit on start-up if necessary.
This requires a service level password for programming
Menu L is a factory menu for configuring the unit's digital inputs and the unit's analog inputs and outputs. This re-
quires the Factory Level password and entry should be limited to Data Aire factory and service personnel.

Menu F - Information

Menu G – Network Config
Menu H – Calibrate Sensors
Menu I – Manual Control
Menu J – Factory Settings
Menu K – Alarms & Limits
RETURN AIR ALARMS
Firestat Set Point:
Hi Temp Alarm:
Setpoint:
Low Temp Alarm:
Setpoint:
Menu L – Configure I/O
150°F
Yes
80°F
Yes
60°F