Dux 135DC5P Manuel du propriétaire - Page 4

Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Dux 135DC5P. Dux 135DC5P 20 pages. Gas hot water heaters

Dux 135DC5P Manuel du propriétaire
Note - all models are equipped
with sacrificial anodes, most are
accessible through the top cover. It is
recommended that a distance of 50% of
the height of the water heater is provided
as clearance above the water heater.
This will assist in the replacement of the
anodes.
Clearances:
Clause 6.9 of AS/NZS 5601.1 specifies
the minimum clearances required
between the water heater and building
features, structures and other items.
As a guide, some of the common
clearance requirements are set out
below:
At least 300 mm below any eaves,
balconies or other projections.
Note that at least half the height of
ELECTRICITY METER
OR FUSE BOX
500mm MIN
2
Owner's Manual – Prodigy 4 & 5
Installation Requirements
500mm MIN
the water heater is recommended as
clearance to provide access to the
anode.
At least 500 mm from any external
corner.
At least 500 mm from any return
wall or other structure facing the
side of the water heater.
At least 1000 mm from any gas
meter.
At least 500 mm from any electricity
meter or fuse box.
At least 500 mm from any openable
window or door.
For a full list of the requirements and
exemptions please refer to
AS/NZS 5601.1.
GAS METER
300mm MIN
1000mm MIN
500mm MIN
500mm MIN
WINDOW OR
OTHER OPENING
DOOR
500mm MIN
H3109
3109
Rev. L